| 2018-12-21 16:34:23 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18110877 |
| | REVIEWED: DECEMBER 21, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC EXISTING 504.1]STATE THE LEVEL OF ALTERATION |
| | FOR WORK BEING PERFORMED. THIS LOOKS A LEVEL 2 |
| | ALTERATION SINCE WALLS ARE BEING REMOVED. |
| | |
| | 2. [FBC AMENDED 107.3.5] |
| | PROVIDE DESIGN DATA FOR OPENINGS |
| | WIND SPEED V ULT = (170) |
| | WIND SPEED V ASD = (132) |
| | EXPOSURE CATEGORY = B |
| | BUILDING CLASSIFICATION = ENCLOSED |
| | MEAN BLDG. HGT. = ? |
| | PLEASE PROVIDE AN OPENING SCHEDULE TO SHOW THE SIZES |
| | AND DESIGN PRESSURES. |
| | PRESSURES CAN BE USED FROM R301.2(2) WALL ZONE 4 OR 5 |
| | AS APPROPRIATE. |
| | |
| | 3. [FBC AMENDED 107.3.5]PROVIDE IN-FILL DETAIL WHERE |
| | CMU WALL IS BEING CLOSED UP. INCLUDE EXTERIOR FINISH, |
| | DOWELS AND INTERIOR INSULATION/FINISH. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |