| Plan Review Notes For Permit 18110855 |
| Permit Number |
18110855 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-12-14 13:15:31 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) THE INSTALLATION SHALL COMPLY WITH NFPA 24.STANDARD | | | FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND | | | THEIR APPURTENANCES, 2013 EDITION | | | | | | PLEASE ENSURE COMPLIANCE AND PROVIDE AN INDICATING NOTE | | | ON THE RESUBMITTED DRAWINGS. | | | | | | | | | | | | 2) DO NOT COVER OVER ANY JOINTS PRIOR TO FIRE | | | INCPECTION. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | |
|