| Plan Review Notes For Permit 18110855 |
| Permit Number |
18110855 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-11-21 12:17:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED DOCUMENTS DO NOT SHOW ANY SITE PLAN | | | INFORMATION AND/OR LOCATIONS OF THE INSTALLATION | | | EQUIPMENT. | | | | | | REGARDLESS OF WHAT MAY HAVE BEEN SUBMITTED WITH THE | | | MASTER PERMIT, SITE PLAN DRAWINGS ARE REQUIRED THAT | | | SHOW THE EXACT LOCATIONS OF ALL PIPING, VALVES, | | | TURNS/CORNERS, HYDRANTS, FDC'S, CONNECTION POINTS, | | | BACKFLOW, ETC. | | | | | | PLEASE REVIEW AND RESUBMIT DETAILED DRAWINGS. | | | | | | | | | | | | 2) THERE IS NO INDICATION OF COMPLIANCE WITH NFPA | | | 24.STANDARD FOR THE INSTALLATION OF PRIVATE FIRE | | | SERVICE MAINS AND THEIR APPURTENANCES, 2013 EDITION | | | | | | PLEASE ENSURE COMPLIANCE AND PROVIDE AN INDICATING NOTE | | | ON THE RESUBMITTED DRAWINGS. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|