2018-11-21 12:17:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED DOCUMENTS DO NOT SHOW ANY SITE PLAN
 INFORMATION AND/OR LOCATIONS OF THE INSTALLATION
 EQUIPMENT.
  
 REGARDLESS OF WHAT MAY HAVE BEEN SUBMITTED WITH THE
 MASTER PERMIT, SITE PLAN DRAWINGS ARE REQUIRED THAT
 SHOW THE EXACT LOCATIONS OF ALL PIPING, VALVES,
 TURNS/CORNERS, HYDRANTS, FDC'S, CONNECTION POINTS,
 BACKFLOW, ETC.
  
 PLEASE REVIEW AND RESUBMIT DETAILED DRAWINGS.
  
  
  
 2) THERE IS NO INDICATION OF COMPLIANCE WITH NFPA
 24.STANDARD FOR THE INSTALLATION OF PRIVATE FIRE
 SERVICE MAINS AND THEIR APPURTENANCES, 2013 EDITION
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN INDICATING NOTE
 ON THE RESUBMITTED DRAWINGS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL