2018-12-17 08:16:581ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110788
 12/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: PLEASE LABEL THE NEW HEAT PUMP AS EITHER
 NEW OR REPLACEMENT. PLEASE NOTE AC COOLING AND HEATING
 CALCULATIONS ATRE REQUIRED FOR NEW INSTALLATIONS-
 SECTION C403.2.1 FBC EC.
  
 2) M2.1: PLEASE LABEL THE CONDENSATE PIPING LINE AND
 INDICATE THE TYPE OF PIPING TO BE INSTALLED- SECTIONS
 307.2 AND 606.2.2.1 FBC M.
  
 3) COMPLY WITH ELECTRICAL COMMENT CONCERNING JOB VALUE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  