| Plan Review Notes For Permit 18110768 |
| Permit Number |
18110768 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-03-13 08:12:08 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND REVIEW | | | RESULTS DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT. | | | | | | 1. OK | | | 2. OK | | | 3. OK PER RED-LINED PLANS. FBC R 322.2.2.1 THE FLOOD | | | VENTS NEED TO BE INSTALLED ON DIFFERENT SIDES. | | | 4. FAIL ENERGY SUBMITTALS STILL NEED TO BE SIGNED BY | | | OWNER AGENT. | | | 5. OK A SEPERATE PERMIT IS REQUIRED FOR THE POOL. | | | 6. OK A SEPERATE PERMIT IS REQUIRED FOR THE GENERATOR. | | | 7. OK WITH PROVISO THE PRODUCT APPROVALS FOR WINDOWS | | | AND DOORS WILL BE REQUIRED PRIOR TO INSPECTION. | | | 8. FAIL PALM BEACH COUNTY IMPACT FEES ARE STILL | | | PENDING. | | | 9. FAIL THE SUBMITTED ELEVATION CERTIFICATION NEEDS TO | | | BE RE-EVALUATED, CORRECTED, AND RE-SUBMITTED. | | | SECTION A9(B) FBC R 322.2.2.1 NEEDS TO BE CORRECTED. | | | SECTION A9(C) FBC R 322.2.2 NEEDS TO BE CORRECTED. | | | SECTION B6 DATE IS NOT CORRECT (OUR RECORDS SHOW | | | 10/5/2017). | | | SECTION B7 DATE IS NOT CORRECT (OUR RECORDS SHOW | | | 10/5/2017). | | | SECTION C2(A) IS NOT CORRECT (THIS SHOULD BE AT 8.00'). | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. |
|