| 2018-12-26 11:06:02 | GAS PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. FLOOR PLAN FOR FUTURE GENERATOR INDICATES IT WILL |
| | REQUIRE 221,000 BTU'S. ISOMETRIC FOR FUTURE GENERATOR |
| | INDICATES IT WILL REQUIRE 352,000 BTU'S. PLEASE |
| | CLARIFY. |
| | |
| | 2. PLACE NOTE ON ISOMETRIC DRAWING THAT THE POOL HEATER |
| | AND GENERATOR ARE FOR FUTURE USE. |
| | |
| | 3. PROVIDE TOTAL DISTANCE NOTE FROM GAS DELIVERY TO |
| | FARTHEST APPLIANCE ON ISOMETRIC NOTES, PLAN PAGE P-2. |
| | |
| | 4. ISOMETRIC INDICATE A 1 INCH PLASTIC LINE GOING UNDER |
| | THE SLAB. THIS IS NOT ALLOWED PER 402.4. |
| | |
| | 5. FLOOR PLAN INDICATES GAS DRYER REQUIRES 40,000 |
| | BTU'S. ISOMETRIC INDICATES GAS DRYER REQUIRES 20,000 |
| | BTU'S. PLEASE CLARIFY. |
| | |
| | 6. PROVIDE MANUFACTURERS SPECIIFCATIONS FOR ALL GAS |
| | APPLIANCES. |
| | |
| | 7. GENERAL NOTE: ALL EXTERIOR GAS APPLIANCES SHALL BE |
| | AT LEAST 4 FEET AWAY FROM ANY DOOR OR WINDOW OPENING. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |