| 2018-12-07 12:41:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE |
| | OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING |
| | UNIT. NEC 210.52(E)(3); FBC RE E3901.7 |
| | 2. RISER DIAGRAM SHOWS THE FEED TO THE GENERATOR WITH A |
| | #10 EQUIPMENT GROUNDING CONDUCTOR. THIS IS NOT THE |
| | CORRECT SIZE FOR A FEED WITH A 125 AMP BREAKER ON |
| | GENERATOR AS SHOWN. PROVIDE CORRECTION. NEC 250.122; |
| | FBC RE E3704.6 |
| | 3. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| | BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| | FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| | R314.3(4), NFPA 72:29.8.3.4 |
| | 4. THERE ARE 3 LIGHTS SHOWN OUTSIDE THAT APPEAR TO BE |
| | IN THE POOL, SWITCHED FROM INSIDE THE HOUSE. ARE THESE |
| | IN FACT POOL LIGHTS, RATED TO BE IN THE POOL, OR IS |
| | THIS SOMETHING THAT WILL BE MOUNTED ABOVE THE POOL? |
| | PROVIDE CLARIFICATION AND COMPLIANCE WITH FBC RE E4203 |
| | IF NECESSARY. WPB FBC 107.2.1; NEC 680.22; FBC RE |
| | E4203.4 |
| | 5. BASED ON THE OUTLINE OF POOL SHOWN ON PLAN, THERE |
| | ARE GFCI RECEPTACLES THAT ARE TOO CLOSE TO THE POOL |
| | WATER. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC |
| | 680.22; FBC RE E4203.1 |
| | 6. ALL GROUNDING ELECTRODES PRESENT MUST BE BONDED |
| | TOGETHER. THE CONCRETE ENCASED ELECTRODE IS NOT SHOWN |
| | ON RISER DIAGRAM. PROVIDE CORRECTION. NEC 250.52; FBC |
| | RE E3608.1 |
| | 7. ALL RECEPTACLE OUTLETS IN BATHROOM MUST BE GFCI |
| | PROTECTED. PROVIDE CORRECTION FOR MASTER BATH TOILET |
| | AREA. NEC 210.8; FBC RE E3902.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |