Plan Review Notes
Plan Review Notes For Permit 18110762
Permit Number 18110762
Review Stop B
Sequence Number 2
Notes
Date Text
2019-01-23 08:03:32BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE FOUNDATION PLAN SHEET 1 OF 19, SIGNED AND SEALED
 BY DESIGNER OF RECORD SHOWS THE GENERATOR PAD, DETAIL B
 WITH THE FOLLOWING NOTE: 86X44X4 INCH CONCRETE
 GENERATOR PAD. SEE FOUNDATION NOTES FOR CONCRETE
 SPECIFICATIONS. THERE ARE NOE SPECIFICATIONS PROVIDE ON
 THE APPROVED SET OF DRAWINGS. THERE IS A SEPERATE SHEET
 PRODUCED BY HAWKES & DANIEL CONSTRUCTION, INC. WITH
 CONCRETE SPECIFICATIONS AND AN ATTACHMENT DETAIL.
 2. DESIGNER TO EITHER PRODUCE CONCRETE SPECIFICATIONS
 AND ATTACHMENT DETAIL ON APPROVED SET OF PLANS OR
 REVIEW AND APPROVE DETAIL PROVIDED BY CONTRACTOR BY
 SIGNING AND SEALING PLAN.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  