| 2019-01-17 08:43:17 | 01/17/19 REVISED COMMENTS. |
| | |
| | |
| | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- IT LOOKS LIKE THE 1415 N. SAPODILLA ADDRESS MAY NEED |
| | TO BE CHANGED WITH AN APPROVED ADDRESS IDENTIFICATION |
| | AS REQUIRED BY SEC. R319.1 FBC RESIDENTIAL. |
| | TYPICALLY, THE ADDRESS IS GIVEN BASED ON THE STREET |
| | FACING THE ENTRY OF THE BUILDING. THE PROPOSED BUILDING |
| | ENTRANCE IS FACING 14TH STREET. THERE WERE THREE |
| | BUILDINGS IN THIS PARCEL AND THEY WERE DEMOLISHED. THE |
| | ADDRESS FOR THE BUILDING FACING 14 STREET WAS 702 14TH |
| | STREET. IT LOOKS LIKE THE 702 14TH STREET ADDRESS WILL |
| | BE MORE SUITABLE. PLEASE CONTACT MIKE ORIO CITY OF WEST |
| | PALM BEACH GIS SUPPORT SPECIALIST TO GET APPROVED |
| | ADDRESS. |
| | SEE CONTACT INFORMATION BELOW. |
| | |
| | CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/ |
| | INFORMATION TECHNOLOGY |
| | TEL: 561-494-1040 |
| | E-MAIL: [email protected] |
| | |
| | 2- PROVIDE SURVEY WITH SURVEYORS ORIGINAL SEAL AND |
| | SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. OR SUBMIT |
| | SURVEY WITH DIGITAL SIGNATURE. |
| | |
| | 3- REVISE ENERGY CALCULATIONS: |
| | A) ITEM #5 ON PAGE 1 OF 5 STATES THAT THIS IS NOT WORST |
| | CASE SCENARIO. PAGE 2 OF 4 STATES THAT THE HOUSE WAS |
| | ROTATED 180 DEGREES. CALCULATIONS NEED TO BE DONE BASED |
| | ON THE ACTUAL ORIENTATION OF THE BUILDING OR PROVIDE |
| | THE CALCULATIONS FOR WORST CASE SCENARIO AS ALLOWED BY |
| | THE EXCEPTION ON SEC. R405.4.2.1 FBC-ENERGY |
| | CONSERVATION. REVISE AS REQUIRED. |
| | |
| | B)WALL INSULATION DOESN'T MATCH PLANS. |
| | |
| | C) PROVIDE THE NAME OF THE OWNER. REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D) PROVIDE THE NAME OF THE PERSON PERFORMING THE ENERGY |
| | CALCULATIONS. REVISE AS REQUIRED. SEC. R405.4.2.1 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E) EXTERIOR DOORS ORIENTATION DON'T MATCH PLANS. EVEN |
| | IF DOING CALCULATIONS FOR WORST CASE SCENARIO. REVISE |
| | AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F)WINDOWS INFORMATION IS INCORRECT. REVISE THE WINDOW |
| | ORIENTATION, WINDOW AREA AND WINDOW OVERHANG DEPTH AND |
| | SEPARATION TO MATCH PLANS. REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | G) PROVIDE MANUFACTURER'S INFORMATION SHOWING THE |
| | WINDOWS EFFICIENCIES SPECIFIED ON THE FIRST PAGE OF THE |
| | ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.3 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS SHOWING THE SHGC FACTOR |
| | SPECIFIED IN THE ENERGY CALCULATIONS WILL BE REQUIRED |
| | FOR INSPECTION. |
| | |
| | 4- UNABLE TO SEE SOIL TEST REPORT. IT WAS NOT UPLOADED. |
| | PROVIDE SOIL TEST REPORT. SEC. R401.4 FBC-RESIDENTIAL. |
| | |
| | 5- VALUATION DECLARED IN THE PERMIT APPLICATION WAS |
| | UPDATED TO $184,578. AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. THE PERMIT FEE BALANCE IS $1,841.08. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |