Plan Review Notes
Plan Review Notes For Permit 18110737
Permit Number 18110737
Review Stop P
Sequence Number 1
Notes
Date Text
2018-12-07 15:46:291) SHT. 4 OF 6 - VACUUM FITTING DETAIL NOTE REFERS TO
 THE 2004 FLORIDA BUILDING CODE. TTHE CODE IN EFFECT IS
 THE 2017 EDITION. IN ADDITION, SEC. 424 DOES NOT APPLY
 TO SWIMMING POOLS.REVISE THE NOTE.
 2) OPEN TYPE GUTTERS SHALL COMPLY WITH 2017
 FBC-BUILDING SEC.454.1.6.5.3.1.1. GUTTERS SHALL BE A
 MINIMUM OF 6 INCHES DDEEP AND 12 INCHES WIDE. GUTTERS
 SHALL SLOPE 2 INCHES FROM THE LIP TO THE DRAIN. PROVIDE
 THIS INFORMATION ON THE PLANS.
 3) SUBMIT TWO COPIES OF THE MAIN DRAIN SPECIFICATIONS
 FOR REVIEW. THE MAIN DRAIN SHALL COMPLY WITH ANSI/APASP
 16.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATER, CHLORINE FEEDERS, & PH FEEDER. FEEDERS SHALL
 MEET THE REQUIREMENTS OF ANSI/NSF 50 PER 2017 FBC SEC.
 454.1.6.5.16.
 5) CHEMICALS SHALL BE ADDED TO THE RETURN LINES AFTER
 THE PUMP, HEATER AND FILTERS PER 2017 FBC-BUILDING
 SEC.454.1.6.5.16. SHOW THIS ON THE PIPING PLAN.
 6) THE PH FEEDER HAVE AN INTERLOCK WITH THE CIRCULATION
 PUMP PER 2017 FBC-BUILDING SEC.454.1.6.5.16.3.
 7) THE RECIRCULATION PUMP SHALL BE SELF-PRIMING IF IT
 IS LOCATED ABOVE THE WATER LEVEL OF THE POOL. 2017
 FBC-BUILDING SEC. 454.1.6.5.4. INDICATE ON THE PLAN.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CARTRIDGE FILTERS. FILTERS SHALL BE EQUIPPED WITH AN
 AIR RELIEF VALVE. 2017 FBC-BUILDING
 SEC.454.1.6.5.5.2.1.
 9) SUBMIT TWO COPIES OF THE POOL HEATER IF ONE IS TO BE
 INSTALLLED AND SHOW IT ON THE PLAN.
 10) SUBMIT A PIPING RISER FOR THE POOL EQUIPMENT. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  