| 2018-12-11 08:40:14 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18110726 |
| | 12/11/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE MAIN PERMIT PLANS FOR THE MEDICAL REHAB |
| | RENOVATION SHOWS THE GREASE DUCT TO BE ENCLOSED IN A |
| | 2HR RATED FIRE WRAPPING. THE SUBMITTED HOOD PLANS SHOW |
| | A 3" CLEARANCE REDUCTION METHOD PER NFPA 96 WHERE THE |
| | DUCT PENETRATES THE COMBUSTIBLE ROOF ASSEMBLY. THE |
| | ENGINEER OF RECORD FOR THE MEDICAL WAY REHAB ERIC |
| | SVOBODA PE. MUSTL PROVIDE A SHOP DRAWING APPROVAL ON |
| | THE PLANS- SECTION 107.2.1 WPB. |
| | |
| | 2) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M MAKEUP |
| | AIR TEMPERATURE. |
| | |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F |
| | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS |
| | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE |
| | HVAC SYSTEM. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |