2018-11-16 17:30:24RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R22
 SUBMITTED:
 THE MAXIMUM DESIGN PRESSURES FOR BONDED INSULATED
 SELECTED ASSEMBLY W-1 ON PAGE 5 OF 58 ARE -52.5PSF.
 BONDED ASSEMBLIES DON'T ALLOW RATIONAL ANALYSIS TO
 INCREASE THE DESIGN PRESSURES. SEE NOTE #10 ON PAGE 2
 OF 58. THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES AS REQUIRED BY SEC. R301.1
 FBC-RESIDENTIAL. THEREFORE, THIS ASSEMBLY CAN NOT BE
 USED. NEED TO PROVIDE ANOTHER PRODUCT APPROVAL FOR
 ASSEMBLY THAT MEETS OR EXCEEDS THE DESIGN PRESSURES FOR
 ALL ROOF ZONES.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION ($1500)
 FOR THE ADDITIONAL WORK SEEMS TO BE LOW FOR A FLAT ROOF
 WITH INSULATION. SEC. 109.3 CITY AMENDMENTS. SPECIFY
 HOW MUCH FLAT ROOF AREA IS GOING TO BE RE-ROOFED.
 VALUATION WILL BE ADJUSTED ACCORDINGLY. OR PROVIDE COPY
 OF SIGNED CONTRACT FOR BUILDING OFFICIAL
 REVIEW/APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  