Plan Review Notes
Plan Review Notes For Permit 18110692
Permit Number 18110692
Review Stop M
Sequence Number 1
Notes
Date Text
2018-12-26 17:11:111ST REVIEW FBC-2017 MECHANICAL
 REVISION #18110692
 MASTER PERMIT #17120261
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M2-2-A, M2-2-B, M2-3A, M8-1, AND MEPO-1 THAT
 ARE LISTED IN THE NARRATIVE WERE NOT UPLOADED IN THE
 SETS FOR REVIEW. PLEASE PROVIDE THE SHEETS.
  
 2) M2-1-B: PLEASE SHOW THE CLEARANCE DISTANCE BETWEEN
 THE WATER HEATER AIR INTAKE AND EXHAUST TERMINATION-
 SECTION 503.8 FBC FG.
  
 3) COMMENTS #1 & 2 FROM THE MECHANICAL REVIEW FOR
 REVISON #18100350 STILL EXIST. I HAVE COPIED THEM BELOW
 AS THEY APPLY TO THIS REVISION ALSO.
  
 1) PLEASE PROVIDE AN ITEMIZED LIST OF ADDITIONAL
 MECHANICAL EQUIPMENT AND LABOR COSTS FOR THE NEW
 OSCILLATING FANS, THE AIR CURTAINS, AND LARGER MODEL
 IRH UNITS.
  
 2) SHOW THE HEIGHTS OF THE NEW FANS AND HEATERS FROM
 THE FINISH FLOOR TO THE BOTTOM OF THE UNITS- SECTION
 1003.3 FBC B.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  