| 2018-12-26 17:11:11 | 1ST REVIEW FBC-2017 MECHANICAL |
| | REVISION #18110692 |
| | MASTER PERMIT #17120261 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M2-2-A, M2-2-B, M2-3A, M8-1, AND MEPO-1 THAT |
| | ARE LISTED IN THE NARRATIVE WERE NOT UPLOADED IN THE |
| | SETS FOR REVIEW. PLEASE PROVIDE THE SHEETS. |
| | |
| | 2) M2-1-B: PLEASE SHOW THE CLEARANCE DISTANCE BETWEEN |
| | THE WATER HEATER AIR INTAKE AND EXHAUST TERMINATION- |
| | SECTION 503.8 FBC FG. |
| | |
| | 3) COMMENTS #1 & 2 FROM THE MECHANICAL REVIEW FOR |
| | REVISON #18100350 STILL EXIST. I HAVE COPIED THEM BELOW |
| | AS THEY APPLY TO THIS REVISION ALSO. |
| | |
| | 1) PLEASE PROVIDE AN ITEMIZED LIST OF ADDITIONAL |
| | MECHANICAL EQUIPMENT AND LABOR COSTS FOR THE NEW |
| | OSCILLATING FANS, THE AIR CURTAINS, AND LARGER MODEL |
| | IRH UNITS. |
| | |
| | 2) SHOW THE HEIGHTS OF THE NEW FANS AND HEATERS FROM |
| | THE FINISH FLOOR TO THE BOTTOM OF THE UNITS- SECTION |
| | 1003.3 FBC B. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |