| 2019-05-02 14:20:30 | PLUMBING 4TH REVIEW**DENIED**FL ST 553.80 (B)2B WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) ANSWERED |
| | |
| | 2) 3RD REQUEST .PROVIDE CLEAR FLOOR SPACE ON SHT. A-1 |
| | FOR 1 OF THE 2 LOBBY HAND SINKS, . FBC-A 212.2, 606 |
| | |
| | 3) 3RD REQUEST .PROVIDE CLEAR FLOOR SPACE FOR THE |
| | DRINKING FOUNTAIN ON SHT. A-1 FBC 107.3.5 |
| | |
| | 4) 3RD REQUEST. PROVIDE INSTALLATION MANUAL FOR THE |
| | LINT INTERCEPTOR. FBC 107.2.1 |
| | |
| | 5) ANSWERED |
| | |
| | 6) ANSWERED |
| | |
| | 7) 3RD REQUEST. NO RESPONSE PROVIDED NO INSTALLATION |
| | MANUALS PROVIDED. PROVIDE PEDICURE CHAIRS SPEC SHEETS |
| | AND INSTALLATION MANUAL'S. FBC 107.3.5 |
| | |
| | 8) 2ND REQUEST. SHT P-1 IIS NOW SEALED BUT STILL NOT |
| | SIGNED . FAC 61G15-23.001 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |