| 2018-12-13 12:05:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18110671 |
| | 12/14/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-2: AN ENERGY RECOVERY VENTILATOR IS REQUIRED |
| | FOR THE NAIL SALON EXHAUST SYSTEM IN COMPLIANCE WITH |
| | SECTION C403.2.7 FBC EC. PLEASE CORRECT THE PLANS AND |
| | CALCULATIONS ACCORDINGLY. |
| | |
| | 2) M-2: REFER TO TABLE 403.3.1.1 AND FOOTNOTE H UNDER |
| | THE TABLE AND PROVIDE AN EXHAUST VENTILATION |
| | CALCULATION FOR THE PROPOSED SPACE AT THE REQUIRED RATE |
| | OF 0.60 CFMS PER SF. PLEASE NOTE THE FOLLOWING: A) THE |
| | CURRENT EXHAUST SYSTEM INDICATED AT 1000 CFRMS DOES NOT |
| | MEET THE REQUIRED 0.60 CFMS PER SF RATE REQUIRED RATE |
| | SO ADDITIONAL EXHAUST MUST BE PROVIDED. B) IT IS |
| | REQUIRED THAT THE EXHAUST SYSTEM RUN CONTINOULSY DURING |
| | OCCUPANCY HOWEVER THE SEQUENCE OF OPERATION FOR THE |
| | SYSTEM HAS NOT BEEN ADDRESSED ON THE PLANS- SEE SECTION |
| | 501.4 FBC M. PLEASE NOTE THAT INSTALLATION OF THE ERV |
| | MAY RESOLVE THIS ISSUE BECAUSE IT WILL HAVE TO BE |
| | CONNECTED TO THE AC SYSTEM. |
| | |
| | 3) M-1, M-2: BASED ON THE NUMBER OF PEDICURE CHAIRS, IT |
| | APPEARS THAT THE 38 PERSON OCCUPANT LOAD WHICH IS SHOWN |
| | ON THE LIFE SAFETY PLANS AND THE O/A TABLE IS |
| | INCORRECT. PEDICURE CHAIRS WERE COUNTED AS ONE |
| | OCCUPANT, HOWEVER THE CHEMICAL APPLICATOR AT EACH CHAIR |
| | WAS NOT COUNTED. |
| | |
| | 4) M-1: REFER TO TABLE 403.3.1.1 FOOTNOTE B: THE PLAN |
| | SHOWS RECIRCULATION OF AIR FROM THE SALON TO THE |
| | BREAKROOM, FACIAL ROOM, AND THE TOILET ROOMS WHICH IS |
| | PROHIBITED. |
| | |
| | 5) M-2: CLARIFY HOW THE SOURCE CAPTURE SYSTEM FOR THE |
| | PEDICURE CHAIRS WILL BE IN COMPLIANCE WITH SECTION |
| | 502.20 WHICH REQUIRES THE EXHAUST INLET TO BE LOCATED |
| | NOT MORE THAN 12 INCHES HORIZONTALLY AND VERTICALLY |
| | FROM THE POINT OF CHEMICAL APPLICATION. THE CURRENT |
| | PLAN AND DETAILS INDICATE THE INLETS ON THE FLOOR UNDER |
| | THE CHAIRS. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER |
| | PER SECTION 504.1 FBC M. A) INDICATE THE TOTAL RUN |
| | LENGTH OF THE DRYER VENT- SECTION 504.8.4. B) PLEASE |
| | NOTE THAT MAKEUP AIR MAY BE REQUIRED- SECTION 504.6. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |