Notes
Date Text
2018-11-19 15:16:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED CALCULATIONS SHEETS DO NOT CLEARLY
 INDICATE THE SAFETY FACTOR OF THIS PROPOSED
 INSTALLATION.
  
 PLEASE PROVIDE THE REMAINING SAFETY FACTOR OF THE
 PROPOSED.
  
  
  
 2) THERE ARE FLEX HOSE PROPOSED; HOWEVER, THERE ARE NO
 INDICATIONS OF MODEL TYPE(S) INDICATED.
  
 PLEASE INDICATED WHICH FLEX HOSE TYPES ARE BEING USED
 (ARE THEY ALL THE SAME?) TO ENSURE THAT THE CORRECT
 FRICTION LOSS IS PROVIDED AS EACH LOCATION?
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  