| Plan Review Notes For Permit 18110667 |
| Permit Number |
18110667 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-11-19 15:16:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED CALCULATIONS SHEETS DO NOT CLEARLY | | | INDICATE THE SAFETY FACTOR OF THIS PROPOSED | | | INSTALLATION. | | | | | | PLEASE PROVIDE THE REMAINING SAFETY FACTOR OF THE | | | PROPOSED. | | | | | | | | | | | | 2) THERE ARE FLEX HOSE PROPOSED; HOWEVER, THERE ARE NO | | | INDICATIONS OF MODEL TYPE(S) INDICATED. | | | | | | PLEASE INDICATED WHICH FLEX HOSE TYPES ARE BEING USED | | | (ARE THEY ALL THE SAME?) TO ENSURE THAT THE CORRECT | | | FRICTION LOSS IS PROVIDED AS EACH LOCATION? | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|