Plan Review Notes
Plan Review Notes For Permit 18110642
Permit Number 18110642
Review Stop G
Sequence Number 2
Notes
Date Text
2019-02-12 09:59:471) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
 SPECIFICATION SHEETS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE STRUCTURE SHALL BE APPROVED FOR OUTDOOR
 USE.2ND REQUEST. WPB AMEND. TO FBC SEC. 107.2.1, 2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 2) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. 2ND
 REQUEST.
 3) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-FUEL GAS SEC.410.2.(7). 2ND REQUEST
 4) THE SHEETS THAT HAVE BEEN SUBMITTED FROM AN
 INSTALLATION MANUAL HAVE BEEN UPDATED. SUBMIT SHEETS
 #14-16 OF THE MANUAL WHICH SHOWS THE CLEARANCES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  