| Plan Review Notes For Permit 18110642 |
| Permit Number |
18110642 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-02-12 09:59:47 | 1) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS AND | | | SPECIFICATION SHEETS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE STRUCTURE SHALL BE APPROVED FOR OUTDOOR | | | USE.2ND REQUEST. WPB AMEND. TO FBC SEC. 107.2.1, 2017 | | | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. | | | 2) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF | | | EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. 2ND | | | REQUEST. | | | 3) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP | | | REGULATOR. 2017 FBC-FUEL GAS SEC.410.2.(7). 2ND REQUEST | | | 4) THE SHEETS THAT HAVE BEEN SUBMITTED FROM AN | | | INSTALLATION MANUAL HAVE BEEN UPDATED. SUBMIT SHEETS | | | #14-16 OF THE MANUAL WHICH SHOWS THE CLEARANCES. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|