| Plan Review Notes For Permit 18110642 |
| Permit Number |
18110642 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-12-07 09:13:02 | 1) SUBMIT TWO COPIES OF THE GAS PLAN AND ALL DOCUMENTS. | | | WPB AMEND. TO FBC SEC. 107.1. | | | 2) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS | | | FOR THE REGULATORS. WPB AMEND. TO FBC SEC. 107.1. | | | 3) REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2017 | | | FBC-FUEL GAS SEC.410.1. | | | 4) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF | | | EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. | | | 5) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP | | | REGULATOR. 2017 FBC-FUEL GAS SEC.410.2.(7). | | | 6) PLACE A NOTE ON THE PLAN REFERENCING THE GAS SIZING | | | TABLES BEING USED IN THE DESIGN OF THIS GAS SYSTEM. | | | 7) SHOW THE SIZE OF THE PIPE DOWNSTREAM OF THE | | | REGULATOR AT THE GENERATOR. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|