Plan Review Notes For Permit 18110642
Permit Number 18110642
Review Stop G
Sequence Number 1
Notes
Date Text
2018-12-07 09:13:021) SUBMIT TWO COPIES OF THE GAS PLAN AND ALL DOCUMENTS.
 WPB AMEND. TO FBC SEC. 107.1.
 2) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 FOR THE REGULATORS. WPB AMEND. TO FBC SEC. 107.1.
 3) REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2017
 FBC-FUEL GAS SEC.410.1.
 4) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4.
 5) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-FUEL GAS SEC.410.2.(7).
 6) PLACE A NOTE ON THE PLAN REFERENCING THE GAS SIZING
 TABLES BEING USED IN THE DESIGN OF THIS GAS SYSTEM.
 7) SHOW THE SIZE OF THE PIPE DOWNSTREAM OF THE
 REGULATOR AT THE GENERATOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  