2018-12-13 07:15:43REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF PLANS FOR THE GENERATOR PAD WITH
 ANCHORING DETAILS FOR WIND LOADS. PRE-FABRICATED PLANS
 ARE REQUIRED TO BE SIGNED AND SEALED BY A FLORIDA
 LICENSED ENGINEER. FBC107.1 GENERAL. SUBMITTAL
 DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS,
 STATEMENT OF SPECIAL INSPECTIONS, GEOTECHNICAL REPORT
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH PERMIT APPLICATION. THE CONSTRUCTION
 DOCUMENTS SHALL BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL WHERE REQUIRED BY CHAPTER 471, FLORIDA
 STATUTES & 61G15 FLORIDA ADMINISTRATIVE CODE OR CHAPTER
 481, FLORIDA STATUTES & 61G1 FLORIDA ADMINISTRATIVE
 CODE. FBC 107.2.1 - INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. FBC-R301.1