| 2019-01-10 10:25:58 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE ADDRESS ON THE PLAN SHEETS IS 221 EDGEWOOD DR |
| | THIS IS INCORRECT THAT ADDRESS DOES NOT EXIST THE |
| | PERMIT APPLICATION STATES THE ADDRESS AS 215 PLEASE |
| | CORRECT ON PLAN SHEETS. PER FBC AMEND TO FBC 107.2.1 |
| | 2. I COULD NOT LOCATE THE MASTER BUILDING PERMIT |
| | APPLICATION IT APPEARS THAT IT DID NOT GET UPLOADED |
| | PLEASE CLARIFY. PER FBC AMEND TO FBC 107.2.1 |
| | 3. A CLEAN OUT IS REQUIRED ANY BRANCH OF THE BUILDING |
| | DRAIN EXISTS THE BUILDING AND CONNECTS TO THE BUILDING |
| | SEWER PLEASE SHOW ON ISOMETRIC DRAWING. PER FBC RES |
| | P3005.2.3 |
| | 4. PLEASE PLACE NOTE ON THE PLANS. [THE SHUT OF VALVES |
| | FOR THE STACKABLE WASHING MACHINE SHALL BE ACCESSIBLE |
| | PER FBC RES P2903.9.3] [THE WATER HEATER AND PIPING |
| | SHALL COMPLY WITH THE FBC ENERGY R403.5] |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |