| 2018-12-06 16:41:19 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | OUTLETS NEEDED AT THE FRONT AND REAR OF STRUCTURE. |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| | BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM |
| | INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE |
| | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE |
| | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE |
| | THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)] |
| | |
| | STRUCTURE SHALL HAVE A GROUNDING SYSTEM INSTALLED PER |
| | E3607.3 |
| | E3607.3 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) |
| | OR BRANCH CIRCUIT(S). |
| | BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH |
| | CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR |
| | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH |
| | SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S) |
| | SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION |
| | E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS |
| | ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING |
| | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) |
| | REQUIRED IN SECTION E3608 SHALL BE INSTALLED. |
| | [250.32(A)] |
| | |
| | MAINS NEED TO BE GROUPED |
| | E3601.6 SERVICE DISCONNECT REQUIRED. |
| | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN |
| | A BUILDING OR OTHER STRUCTURE FROM THE SERVICE ENTRANCE |
| | CONDUCTORS. (230.70) |
| | |
| | SMOKE ALARMS |
| | R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | EXCEPTIONS: |
| | 1.WORK INVOLVING THE EXTERIOR SURFACES OF DWELLINGS, |
| | SUCH AS THE REPLACEMENT OF ROOFING OR SIDING, THE |
| | ADDITION OR REPLACEMENT OF WINDOWS OR DOORS, OR THE |
| | ADDITION OF A PORCH OR DECK, ARE EXEMPT FROM THE |
| | REQUIREMENTS OF THIS SECTION. |
| | 2.INSTALLATION, ALTERATION OR REPAIRS OF PLUMBING OR |
| | MECHANICAL SYSTEMS ARE EXEMPT FROM THE REQUIREMENTS OF |
| | THIS SECTION |