| 2018-12-31 09:07:43 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18110627 |
| | REVIEWED: DECEMBER 28, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO |
| | MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. |
| | CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION. |
| | THE ENERGY CALCULATIONS IN SUPPORTING DOCUMENTS IS LOAD |
| | CALCS ONLY. PLEASE PROVIDE ADDITIONAL CALCULATIOND TO |
| | INCLUDE DATA USED TO DETERMINE HVAC LOAD CALCULATIONS. |
| | |
| | 2. [FBC AMENDED 107.2.1.2]PROVIDE STAIRCASE AND GUARD |
| | RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. |
| | |
| | 3. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR |
| | DOOR 101 103 AND 104, OR INDICATE THAT YOU WOULD LIKE |
| | IT DEFERED. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |