Plan Review Notes
Plan Review Notes For Permit 18110604
Permit Number 18110604
Review Stop E
Sequence Number 3
Notes
Date Text
2019-02-05 13:16:15ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. AFCI PROTECTION SHOWN IN NOTE 24 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 2. NOTE 25 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE PANEL INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3
 4. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3,
 110.9; FBC RE E3603.3
 5. SHOW LOCATION ON PLAN OF SERVICE AND MAIN PANEL. IF
 DISTANCE IS GREATER THAN 8 FEET FROM METER TO MAIN
 PANEL, PROVIDE DISCONNECT OR MAIN BREAKER ON EXTERIOR
 OF RESIDENCE. IF THIS IS THE CASE, PROVIDE EQUIPMENT
 GROUNDING CONDUCTOR TO INTERIOR PANEL. WPB FBC 107.2.1;
 NEC 250.122; FBC RE E3704.6, 3607.3.1
 6. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 7. - CORRECTED
 8. - CORRECTED
 9. NOTE PROVIDED - COMPLETED
 10. - CORRECTED
 11. - CORRECTED
 12. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 - NOT SHOWN
 13. - CORRECTED
 14. - CORRECTED
 15. - CORRECTED
 16. - CORRECTED
 17. - CORRECTED
  
 NEW COMMENTS:
  
 1. - CORRECTED
  
 2. FBC 107.2.1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5) AND F.S. 481.229.
  
  
  