2018-12-15 15:44:38****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 CORRECTIONS:
  
 FBC B 107.1 A ROOFING PERMIT IS REQUIRED.
 FBC B 107.2.1 PLEASE PROVIDE MORE INFORMATION:
 ON PAGE A-2, THE 16"X 16" COLUMN AT REAR PATIO DOES NOT
 APPEAR. PLEASE PROVIDE THE COLUMN IN THE PROPOSED
 LOCATION FOR CLARITY.
 ON PAGE A-2, THE COMPONENT AND CLADDING PRESSURE
 SCHEDULE SHOWS A 9'X 7' GARAGE DOOR. PLEASE PROVIDE THE
 INTENDED LOCATION FOR THIS DOOR OR REMOVE FROM PLAN.
 ON PAGE A-3, THE LOCATION/CONFIGURATION OF THE ATTIC
 ACCESS OPENING IS RUNNING PERPINDICULAR TO THE PROPOSED
 DIRECTION OF ROOF TRUSS. PLEASE RECONFIGURE OR
 RELOCATE,
 ON PAGE A-7 DETAILS A, B, D, AND WITHIN THE SUBMITTED
 ENERGY AND LOAD CALCULATION SUBMITTALS, R-19 AND R-30
 INSULATION BATTS ARE INDICATED ABOVE THE CEILING. ON
 PAGE A-3 NOTES AND IN A SEPERATE SUBMITTAL PACKAGE,
 OPEN CELL SPRAY APPLIED ICENYNE INSULATION HAS BEEN
 SUBMITTED. PLEASE
 CLARIFY
 ON PAGES A-1, A-2, AND A-3 THE WINDOW/DOOR SCHEDULE AND
 OPENING INDICATORS ARE NOT COMPLETE AND DO NOT
 COMPLETELY MATCH.
 MISSING MECHANICAL PAGES.
 FBC B 107.2.5 PROVIDE THE PROPOSED FINISHED FLOOR
 ELEVATION AND EXTERIOR GRADE ELEVATIONS WITH DIRECTION
 OF WATER DRAINAGE/RUN-OFF INDICATORS ON THE
 SURVEY/SITE-PLAN.
  
  
 NOTES:
  
 AT TIME OF INSPECTION, PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR THE INSPECTOR.
  
 FBC R 314 AND 315 LISTED AND LABELED CARBON MONOXIDE
 AND SMOKE DETECTORS ARE REQUIRED.
  
 AWS D1.1 CLAUSE 3.1 AND 4.15 AT TIME OF INSPECTION, FOR
 THE STEEL COLUMN, PROVIDE A WELD PROCEDURE
 SPECIFICATION; (SPECIFIES THE ESSENTIAL VARIABLES
 INCLUDING: BASE MATERIALS, THE JOINTS, THE WELDING
 PROCESS, AND THE FILLER METALS TO BE USED).
 ALSO, PROVIDE THE WELDERS PERFORMANCE QUALIFICATION
 RECORD; (SHOWS THE WELDER IS QUALIFIED & CERTIFIED FOR
 THE DESCRIBED TYPE OF WELDING REQUIRED ON THIS
 PROJECT).
  
 THE TRUSS ENGINEERING PACKAGE.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL FORM.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS
 DETACHED.
  
  
  
  
  
  