| 2018-12-15 15:44:38 | ****CORRECTIONS**** |
| | |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | CORRECTIONS: |
| | |
| | FBC B 107.1 A ROOFING PERMIT IS REQUIRED. |
| | FBC B 107.2.1 PLEASE PROVIDE MORE INFORMATION: |
| | ON PAGE A-2, THE 16"X 16" COLUMN AT REAR PATIO DOES NOT |
| | APPEAR. PLEASE PROVIDE THE COLUMN IN THE PROPOSED |
| | LOCATION FOR CLARITY. |
| | ON PAGE A-2, THE COMPONENT AND CLADDING PRESSURE |
| | SCHEDULE SHOWS A 9'X 7' GARAGE DOOR. PLEASE PROVIDE THE |
| | INTENDED LOCATION FOR THIS DOOR OR REMOVE FROM PLAN. |
| | ON PAGE A-3, THE LOCATION/CONFIGURATION OF THE ATTIC |
| | ACCESS OPENING IS RUNNING PERPINDICULAR TO THE PROPOSED |
| | DIRECTION OF ROOF TRUSS. PLEASE RECONFIGURE OR |
| | RELOCATE, |
| | ON PAGE A-7 DETAILS A, B, D, AND WITHIN THE SUBMITTED |
| | ENERGY AND LOAD CALCULATION SUBMITTALS, R-19 AND R-30 |
| | INSULATION BATTS ARE INDICATED ABOVE THE CEILING. ON |
| | PAGE A-3 NOTES AND IN A SEPERATE SUBMITTAL PACKAGE, |
| | OPEN CELL SPRAY APPLIED ICENYNE INSULATION HAS BEEN |
| | SUBMITTED. PLEASE |
| | CLARIFY |
| | ON PAGES A-1, A-2, AND A-3 THE WINDOW/DOOR SCHEDULE AND |
| | OPENING INDICATORS ARE NOT COMPLETE AND DO NOT |
| | COMPLETELY MATCH. |
| | MISSING MECHANICAL PAGES. |
| | FBC B 107.2.5 PROVIDE THE PROPOSED FINISHED FLOOR |
| | ELEVATION AND EXTERIOR GRADE ELEVATIONS WITH DIRECTION |
| | OF WATER DRAINAGE/RUN-OFF INDICATORS ON THE |
| | SURVEY/SITE-PLAN. |
| | |
| | |
| | NOTES: |
| | |
| | AT TIME OF INSPECTION, PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION FOR THE INSPECTOR. |
| | |
| | FBC R 314 AND 315 LISTED AND LABELED CARBON MONOXIDE |
| | AND SMOKE DETECTORS ARE REQUIRED. |
| | |
| | AWS D1.1 CLAUSE 3.1 AND 4.15 AT TIME OF INSPECTION, FOR |
| | THE STEEL COLUMN, PROVIDE A WELD PROCEDURE |
| | SPECIFICATION; (SPECIFIES THE ESSENTIAL VARIABLES |
| | INCLUDING: BASE MATERIALS, THE JOINTS, THE WELDING |
| | PROCESS, AND THE FILLER METALS TO BE USED). |
| | ALSO, PROVIDE THE WELDERS PERFORMANCE QUALIFICATION |
| | RECORD; (SHOWS THE WELDER IS QUALIFIED & CERTIFIED FOR |
| | THE DESCRIBED TYPE OF WELDING REQUIRED ON THIS |
| | PROJECT). |
| | |
| | THE TRUSS ENGINEERING PACKAGE. |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY |
| | RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING, |
| | IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING |
| | EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL FORM. |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS |
| | DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |