| Plan Review Notes For Permit 18110552 |
| Permit Number |
18110552 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-12-05 11:37:10 | 1) SHOW THE LOCATION OF ANY OPERABLE DOORS OR WINDOWS | | | ON THE HOUSE PLAN AND SHOW THE DISTANCE OF THE TANKLESS | | | WATER FROM THE DOORS AND WINDOWS. THE LOCATION SHALL | | | COMPLY WITH THE MANUFACTURER'S INSTALLATION MANUAL. | | | 2) THE EXISTING GAS PLANS ON FILE WITH THE CITY SHOW | | | THE DEVELOPED LENGTH TO THE MOST REMOTE GAS OUTLET AS | | | 120 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF | | | THIS SYSTEM. | | | 3) EXISTING PLANS ON FILE IN THE CITY SHOW AN ESIXTING | | | GENERATOR OF 96,000 BTU'S AND BBQ OF 40,000 BTU'S ON | | | THIS SYSTEM. THE BTU LOAD OF THESE TWO APPLIANCES SHALL | | | BE ADDED INTO THE ENTIRE BTU LOAD. 2017 FGC SEC.401.8. | | | 4) THE EXISTING GAS PLAN ON FILE IN THE CITY SHOWS THE | | | OUTLET AT THE METER AS 1 1/2 INCHES AND THE SUBMITTED | | | GAS PLAN SHOWS WHAT APPEARS TO BE 3/4 INCH. CLARIFY. | | | 5) A UNION IS REQUIRED WITHIN ONE FOOT OF EITHER SIDE | | | OF THE GAS REGULATOR. 2017 FGC SEC. 410.2 (7). | | | 6) SUBMIT TWO ENLARGED & LEGIBLE COPIES OF THE | | | REGULATOR SPECS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 7) SUBMIT TWO COPIES OF THE COOKTOP SPECIFICATIONS THAT | | | SHOW THAT THE APPLIANCE IS LISTED AND LABELED. 2017 | | | FBC-FUEL GAS SEC.301.3. | | | NOTE: I HAVE PLACED A COPY OF THE ORIGINAL GAS PLAN IN | | | THE PERMIT APPLICATION FILE . | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|