Plan Review Notes
Plan Review Notes For Permit 18110552
Permit Number 18110552
Review Stop G
Sequence Number 1
Notes
Date Text
2018-12-05 11:37:101) SHOW THE LOCATION OF ANY OPERABLE DOORS OR WINDOWS
 ON THE HOUSE PLAN AND SHOW THE DISTANCE OF THE TANKLESS
 WATER FROM THE DOORS AND WINDOWS. THE LOCATION SHALL
 COMPLY WITH THE MANUFACTURER'S INSTALLATION MANUAL.
 2) THE EXISTING GAS PLANS ON FILE WITH THE CITY SHOW
 THE DEVELOPED LENGTH TO THE MOST REMOTE GAS OUTLET AS
 120 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF
 THIS SYSTEM.
 3) EXISTING PLANS ON FILE IN THE CITY SHOW AN ESIXTING
 GENERATOR OF 96,000 BTU'S AND BBQ OF 40,000 BTU'S ON
 THIS SYSTEM. THE BTU LOAD OF THESE TWO APPLIANCES SHALL
 BE ADDED INTO THE ENTIRE BTU LOAD. 2017 FGC SEC.401.8.
 4) THE EXISTING GAS PLAN ON FILE IN THE CITY SHOWS THE
 OUTLET AT THE METER AS 1 1/2 INCHES AND THE SUBMITTED
 GAS PLAN SHOWS WHAT APPEARS TO BE 3/4 INCH. CLARIFY.
 5) A UNION IS REQUIRED WITHIN ONE FOOT OF EITHER SIDE
 OF THE GAS REGULATOR. 2017 FGC SEC. 410.2 (7).
 6) SUBMIT TWO ENLARGED & LEGIBLE COPIES OF THE
 REGULATOR SPECS. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SUBMIT TWO COPIES OF THE COOKTOP SPECIFICATIONS THAT
 SHOW THAT THE APPLIANCE IS LISTED AND LABELED. 2017
 FBC-FUEL GAS SEC.301.3.
 NOTE: I HAVE PLACED A COPY OF THE ORIGINAL GAS PLAN IN
 THE PERMIT APPLICATION FILE .
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  