| 2018-12-04 14:57:12 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | 1ST REVIEW FBC 2017 EXISTING BUILDING |
| | |
| | BUILDING - FAILED |
| | |
| | FBC 107 PROVIDE CODE INFORMATION. ADD THE FOLLOWING TO |
| | THE PLAN: |
| | |
| | FBC 2017 6TH EDITION |
| | FBC 2017 EXISTING BUILDING |
| | TYPE IIB CONSTRUCTION NON COMBUSTIBLE |
| | OCCUPANCY CLASSIFICATION R-2 |
| | LEVEL II ALTERATION |
| | |
| | PROVIDE A TYPICAL WALL SECTION OF WALLS TO BE ADDED IF |
| | APPLICABLE. |
| | |
| | PROVIDE A FLOORING SUBMITTAL CONSISTING OF INSULATION |
| | TEST REPORTS AND HARD FLOORING TYPE TO SHOW COMPLIANCE |
| | WITH THE FOLLOWING: |
| | |
| | FBC 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE |
| | W/FLAME SPREAD INDEX OF 200 OR LESS. |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | |