2018-12-04 14:57:121ST REVIEW: FBC 2017 6TH EDITION
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 BUILDING - FAILED
  
 FBC 107 PROVIDE CODE INFORMATION. ADD THE FOLLOWING TO
 THE PLAN:
  
 FBC 2017 6TH EDITION
 FBC 2017 EXISTING BUILDING
 TYPE IIB CONSTRUCTION NON COMBUSTIBLE
 OCCUPANCY CLASSIFICATION R-2
 LEVEL II ALTERATION
  
 PROVIDE A TYPICAL WALL SECTION OF WALLS TO BE ADDED IF
 APPLICABLE.
  
 PROVIDE A FLOORING SUBMITTAL CONSISTING OF INSULATION
 TEST REPORTS AND HARD FLOORING TYPE TO SHOW COMPLIANCE
 WITH THE FOLLOWING:
  
 FBC 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED
 FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE
 W/FLAME SPREAD INDEX OF 200 OR LESS.
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  