| Plan Review Notes For Permit 18110485 |
| Permit Number |
18110485 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-01-04 08:55:37 | ****CORRECTIONS**** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | THIS IS THE SECOND BUILDING PLAN REVIEW. PLEASE RESPOND | | | TO THE ITEMS LISTED BELOW. | | | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | | | 1. DESIGN PROFESSIONAL?S (ENGINEER) SIGNATURE & SEAL | | | ARE MISSING FROM PLANS. | | | 2. THE CONCRETE FOOTINGS AND PAD ARE MISSING DIMENSIONS | | | AND REINFORCEMENT/CRACK PREVENTION INFORMATION. | | | 3. THE STRUCTURAL CONNECTIONS ARE NOT COMPLETE : | | | A. A.W.S SECTION/CLAUSE 3.1 PROVIDE A WELD PROCEDURE | | | SPECIFICATION FOR WELDED CONNECTIONS. | | | B. A.W.S SECTION/CLAUSE 4.2.2 PROVIDE WELDERS | | | PERFORMANCE QUALIFICATION RECORD FOR THE WELDING | | | PERSONNEL. | | | C. IN THE CASE THAT SOME OF THE DESCRIBED WELD | | | CONNECTIONS ARE TO BE BOLTED AND/OR SCREWED, PROVIDE | | | DETAILS. |
|