| | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTION 3005.2 FBC B AND SHOW COMPLIANCE |
| | FOR REQUIRED VENTILATION IN THE ELEVATOR MACHINE ROOM. |
| | |
| | 3005.2 VENTING. ELEVATOR MACHINE ROOMS, MACHINERY |
| | SPACES THAT CONTAIN THE DRIVING MACHINE, AND CONTROL |
| | ROOMS OR SPACES THAT CONTAIN THE OPERATION OR MOTION |
| | CONTROLLER FOR ELEVATOR OPERATION SHALL BE PROVIDED |
| | WITH AN INDEPENDENT VENTILATION OR AIR-CONDITIONING |
| | SYSTEM TO PROTECT AGAINST THE OVERHEATING OF THE |
| | ELECTRICAL EQUIPMENT. THE SYSTEM SHALL BE CAPABLE OF |
| | MAINTAINING TEMPERATURES WITHIN THE RANGE ESTABLISHED |
| | FOR THE ELEVATOR EQUIPMENT. |
| | |
| | 2) THE ELEVATOR SHALL BE EQUIPPED WITH AN EXHAUST |
| | SYSTEM SIZED TO PROVIDE 1.0 CFMS OF EXHAUST PER SF.- |
| | TABLE 403.3.1.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |