| 2018-12-13 10:05:07 | ****CORRECTIONS**** |
| | |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | FBC 107. PLEASE PROVIDE MORE INFORMATION : |
| | |
| | 1. THE SUBMITTED PLANS SHOW AN INTERIOR ROOM LABELED |
| | "GARAGE" IN ADDITION TO THE EXISTING GARAGE AT THE |
| | FRONT OF THE HOUSE. PLEASE ADDRESS THIS DISCREPANCY. |
| | |
| | |
| | 2. A SHUTTER PRODUCT APPROVAL WAS SUBMITTED WITHOUT ANY |
| | OTHER REQUIRED INFORMATION: |
| | |
| | A. PROVIDE A SKETCH/LAYOUT SHEET SHOWING THE LOCATION |
| | OF ALL SHUTTERS TO BE INSTALLED.THIS LAYOUT SHEET |
| | SHOULD INDICATE WINDOW/DOOR OPENINGS NUMBERED TO MATCH |
| | WITH THE SCHEDULE FOR INSTALLATION OF OPENING |
| | PROTECTIVE DEVICES. |
| | |
| | |
| | B. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION |
| | OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL |
| | INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL |
| | SPREADSHEET): |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS?PAGE=2 |
| | |
| | C. WHEN COMPLETING THE INSTALLATION SCHEDULE FACTORS |
| | APPLY DEPENDING ON SUBSTRATE, EDGE DISTANCE AND |
| | FASTENER. FOR FASTENER, IF USING TAPCON, BE SPECIFIC AS |
| | TO WHICH TAPCON. |
| | |
| | |
| | D. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC |
| | R 310.4; INCLUDE ROOM DESIGNATION. |