| 2018-11-15 13:02:43 | PERMIT # 18110341 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAILED COMMENT: |
| | |
| | 1) PLEASE PROVIDE A SITE PLAN THAT INDICATES THE |
| | LOCATION OF WHERE THIS TRAILER WILL BE PLACED. PLEASE |
| | BE SURE TO INCLUDE THE LOCATIONS/DIMENSIONS OF OTHER |
| | STRUCTURES ON THE SITE. |
| | |
| | 2) TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS |
| | WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE |
| | FOLLOWING: |
| | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| | PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |