Plan Review Notes
Plan Review Notes For Permit 18110301
Permit Number 18110301
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-04 16:53:10****CORRECTIONS****
 W.P.B. PERMIT: 18110301
 REVIEWED: JANUARY 4, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. 107.5.3 FBC[AMENDED] SHOW ON PLANS WHAT CODE VERSION
 IS BEING USED FOR THE ADDITION, OR TELL ME WHAT SHEET
 THE INFORMATION IS LOCATED ON. PLEASE ADD A GENERAL
 NOTE ON DATA SHEET. ALSO, CHECK CODE VERSION REFERENCED
 ON PLUMBING SHEET.
  
 2. 103.1.1.2 FBC[RE] THE BUILDING'S OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA
 STATUTES.
 A. PLEASE HAVE THE OWNER SIGN THE ENERGY CALCULATIONS.
  
 3. 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE
 INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL
 ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE
 INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL
 SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE
 INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING
 IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR
 CONDENSATION CONTROL.
 A. PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE
 INSULATION AT ROOF DECK.
  
 4. 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND
 LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
 A. PLEASE ADD ROOF PITCH TO ELEVATION, ROOF PLAN OR
 BOTH. IF PITCH IS LESS THAN 4:12 THAN DOUBLE
 UNDERLAYMENT WILL BE REQUIRED.
  
 5. 107.3.4.1 FBC[R] PROVIDE PRODUCT APPROVALS FOR
 ROOFING. I SEE PRODUCT APPROVAL FOR UNDERLAYMENT ONLY
 IN THE SUPPORTING DOCUMENT FOLDER. PLEASE ADD PRODUCT
 APPROVAL FOR ROOFING MATERIAL, OR INDICATE THAT YOU
 WOULD LIKE THEM DEFERED.
  
 6. 107.3.4.1 FBC[R] SUBMIT TRUSS SHOP DRAWINGS TO THE
 BUILDING INSPECTOR PRIOR TO INSTALLATION.
 A. THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 7. 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
 A. PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA. THIS
 WOULD BE LEVEL 3 ALTERATION AND ADDITION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  