| 2019-01-04 16:53:10 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18110301 |
| | REVIEWED: JANUARY 4, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1. 107.5.3 FBC[AMENDED] SHOW ON PLANS WHAT CODE VERSION |
| | IS BEING USED FOR THE ADDITION, OR TELL ME WHAT SHEET |
| | THE INFORMATION IS LOCATED ON. PLEASE ADD A GENERAL |
| | NOTE ON DATA SHEET. ALSO, CHECK CODE VERSION REFERENCED |
| | ON PLUMBING SHEET. |
| | |
| | 2. 103.1.1.2 FBC[RE] THE BUILDING'S OWNER, THE OWNER'S |
| | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED |
| | BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN |
| | COMPLIANCE WITH THE CODE, AS PER SECTION 553.907, |
| | FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO |
| | BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA |
| | STATUTES. |
| | A. PLEASE HAVE THE OWNER SIGN THE ENERGY CALCULATIONS. |
| | |
| | 3. 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED |
| | RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE |
| | INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL |
| | ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE |
| | INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL |
| | SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE |
| | INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING |
| | IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR |
| | CONDENSATION CONTROL. |
| | A. PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE |
| | INSULATION AT ROOF DECK. |
| | |
| | 4. 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM |
| | TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND |
| | LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| | (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED. |
| | A. PLEASE ADD ROOF PITCH TO ELEVATION, ROOF PLAN OR |
| | BOTH. IF PITCH IS LESS THAN 4:12 THAN DOUBLE |
| | UNDERLAYMENT WILL BE REQUIRED. |
| | |
| | 5. 107.3.4.1 FBC[R] PROVIDE PRODUCT APPROVALS FOR |
| | ROOFING. I SEE PRODUCT APPROVAL FOR UNDERLAYMENT ONLY |
| | IN THE SUPPORTING DOCUMENT FOLDER. PLEASE ADD PRODUCT |
| | APPROVAL FOR ROOFING MATERIAL, OR INDICATE THAT YOU |
| | WOULD LIKE THEM DEFERED. |
| | |
| | 6. 107.3.4.1 FBC[R] SUBMIT TRUSS SHOP DRAWINGS TO THE |
| | BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | A. THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN |
| | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE |
| | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE |
| | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | |
| | 7. 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED. |
| | A. PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA. THIS |
| | WOULD BE LEVEL 3 ALTERATION AND ADDITION. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |