| Notes |
| Date |
Text |
| 2019-06-04 15:23:45 | LUMBING COMMEMTS: APPROVED WITH PROVISO | | | 1. PLAN PAGE DET-1, DETAIL 7: SEE REDLINED COMMENTS | | | SIDE WALL HAND RAIL SHALL FALL INTO THE 27" MAXIMUM | | | SPACE CALLED OUT FOR CONTROLS IN ORDER CONFORM TO FBC | | | ACC FIGURE 608.5.2 (B) AS WELL AS FIGURES 608.3.2 (B) | | | AND 608.2.2. | | | 2. PLAN SHEET DET-1, DETAIL 3, 4 AND 8: SEE REDLINED | | | COMMENTS | | | KITCHEN SINK IS PROVIDED WITH A FORWARD APPROACH; | | | PROVIDE KNEE AND TOE CLEARANCE TO CONFORMTO THE | | | REQUIREMENTS OF FBC ACC 306.2 AND 306.3. REFER TO | | | DETAIL 3 WHICH IS APPLICABLE TO BOTH LAVATORIIES AND | | | SINKS. | | | 3. PLAN SHEET P-3, DETAIL 6; SEE REDLINED COMMENT. SINK | | | SHALL MEET DIMENSIONAL REQUIREMENT TO ALLOW IT TO | | | COMPLY WITH THE REQUIREMENTS OF FBC ACC 306.3 | | | | | | | | | A SPECIAL NOTE: THERE IS AN EXISTING GAS METER SHOWN ON | | | A-1. THERE DOES NOT APPEAR TO BE ANY GAS APPLIANCES OR | | | EQUIPMENT IN THE STRUCTURE. IF THERE IS EXISTING GAS | | | PIPING IN THE BUILDING IT MUST BGE RENDERED HARMLESS | | | AND CAPPED TO COMPLIY WITH THE REQUIREMENTS OF THE | | | PUBLIC GAS UTILITIES. A SEPARATE PERMIT WILL BE | | | REQUIRED. | | | |
|