2019-06-04 15:23:45LUMBING COMMEMTS: APPROVED WITH PROVISO
 1. PLAN PAGE DET-1, DETAIL 7: SEE REDLINED COMMENTS
 SIDE WALL HAND RAIL SHALL FALL INTO THE 27" MAXIMUM
 SPACE CALLED OUT FOR CONTROLS IN ORDER CONFORM TO FBC
 ACC FIGURE 608.5.2 (B) AS WELL AS FIGURES 608.3.2 (B)
 AND 608.2.2.
 2. PLAN SHEET DET-1, DETAIL 3, 4 AND 8: SEE REDLINED
 COMMENTS
 KITCHEN SINK IS PROVIDED WITH A FORWARD APPROACH;
 PROVIDE KNEE AND TOE CLEARANCE TO CONFORMTO THE
 REQUIREMENTS OF FBC ACC 306.2 AND 306.3. REFER TO
 DETAIL 3 WHICH IS APPLICABLE TO BOTH LAVATORIIES AND
 SINKS.
 3. PLAN SHEET P-3, DETAIL 6; SEE REDLINED COMMENT. SINK
 SHALL MEET DIMENSIONAL REQUIREMENT TO ALLOW IT TO
 COMPLY WITH THE REQUIREMENTS OF FBC ACC 306.3
  
  
 A SPECIAL NOTE: THERE IS AN EXISTING GAS METER SHOWN ON
 A-1. THERE DOES NOT APPEAR TO BE ANY GAS APPLIANCES OR
 EQUIPMENT IN THE STRUCTURE. IF THERE IS EXISTING GAS
 PIPING IN THE BUILDING IT MUST BGE RENDERED HARMLESS
 AND CAPPED TO COMPLIY WITH THE REQUIREMENTS OF THE
 PUBLIC GAS UTILITIES. A SEPARATE PERMIT WILL BE
 REQUIRED.
  