| | ON REVIEW OF THE PREVIOUS REVIEWS THE FOLLOWING |
| | COMMENTS WILL BE PROVISED: |
| | |
| | PLEASE ENSURE COMPLIANCE WITH THE BELOW COMMENTS AS |
| | THEY WILL INSPECTED BY A FIRE ISNPECTOR FOR |
| | VERIFICATION PURPOSES. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | 5/28/19 |
| | |
| | THE PREVIOUS FIRE PLAN REVIEWER IS NO LONGER WITH THE |
| | CITY. |
| | |
| | BASED ON MY REVIEW OF THE PREVIOUSLY SUBMITTED |
| | INFORMATION, UNFORTUNATLY, THE FOLLOWING COMMENTS ARE |
| | NEEDED FOR CLARIFICATION PURPOSES. |
| | |
| | |
| | |
| | 1) BASED ON WHAT HAS BEEN PREVIOUSLY SUBMITTED, THIS |
| | OCCUPANCY CLASSIFICATION PER THE FLORIDA FIRE |
| | PREVENTION CODE IS LODGING AND ROOMING HOUSE PER NFPA |
| | 101, CH 26. |
| | |
| | PER NFPA 101, CH 3 , DEFINITIONS |
| | |
| | 3.3.167 LODGING OR ROOMING HOUSE. A BUILDING OR PORTION |
| | THEREOF |
| | THAT DOES NOT QUALIFY AS A ONE- OR TWO-FAMILY DWELLING, |
| | THAT PROVIDES |
| | SLEEPING ACCOMMODATIONS FOR A TOTAL OF 16 OR FEWER |
| | PEOPLE ON A |
| | TRANSIENT OR PERMANENT BASIS, WITHOUT PERSONAL CARE |
| | SERVICES, WITH OR |
| | WITHOUT MEALS, BUT WITHOUT SEPARATE COOKING FACILITIES |
| | FOR INDIVIDUAL |
| | OCCUPANTS |
| | |
| | SHOULD YOU DISAGREE PLEASE PROVIDE A DETAILED NARRATIVE |
| | WITH SPECIFIC CODE REFERENCES. |
| | |
| | |
| | 2) THERE ARE NO INDICATION OF A FIRE ALARM SYSTEM. |
| | |
| | PER NFPA 101, CH 26 |
| | |
| | 26.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 26.3.4.1 GENERAL. |
| | 26.3.4.1.1 LODGING AND ROOMING HOUSES, OTHER THAN THOSE |
| | MEETING |
| | 26.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM |
| | IN ACCORDANCE |
| | WITH SECTION 9.6. |
| | 26.3.4.1.2 A FIRE ALARM SYSTEM IN ACCORDANCE WITH |
| | SECTION 9.6 SHALL |
| | NOT BE REQUIRED IN EXISTING LODGING AND ROOMING HOUSES |
| | THAT HAVE AN |
| | EXISTING SMOKE DETECTION SYSTEM MEETING OR EXCEEDING |
| | THE |
| | REQUIREMENTS OF 26.3.4.5.1 WHERE THAT DETECTION SYSTEM |
| | INCLUDES NOT |
| | LESS THAN ONE MANUAL FIRE ALARM BOX PER FLOOR ARRANGED |
| | TO INITIATE THE |
| | SMOKE DETECTION ALARM. |
| | |
| | PLEASE PROVIDE DETAILS AND/OR A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM. |
| | |
| | PER NFPA 101, CH 26 |
| | |
| | 26.3.6 EXTINGUISHMENT REQUIREMENTS. |
| | 26.3.6.1 ALL NEW LODGING OR ROOMING HOUSES SHALL BE |
| | PROTECTED |
| | THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 26.3.6.2. |
| | |
| | PLEASE PROVIDE DETAILS AND/OR A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | |
| | 4) THERE IS ONLY 1 EXIT INDICATED FRON THE 2ND FLOOR. |
| | |
| | PER NFPA 101, CH 26 |
| | |
| | 26.2.1 NUMBER AND TYPES OF MEANS OF ESCAPE. |
| | 26.2.1.1 PRIMARY MEANS OF ESCAPE. |
| | 26.2.1.1.1 EVERY SLEEPING ROOM AND LIVING AREA SHALL |
| | HAVE ACCESS |
| | TO A PRIMARY MEANS OF ESCAPE COMPLYING WITH CHAPTER 24 |
| | AND |
| | LOCATED TO PROVIDE A SAFE PATH OF TRAVEL TO THE |
| | OUTSIDE. |
| | 26.2.1.1.2 WHERE THE SLEEPING ROOM IS ABOVE OR BELOW |
| | THE LEVEL OF |
| | EXIT DISCHARGE, THE PRIMARY MEANS OF ESCAPE SHALL BE AN |
| | INTERIOR |
| | STAIR IN ACCORDANCE WITH 26.2.2, AN EXTERIOR STAIR, A |
| | HORIZONTAL EXIT |
| | IN ACCORDANCE WITH 7.2.4, OR AN EXISTING FIRE ESCAPE |
| | STAIR IN |
| | ACCORDANCE WITH 7.2.8. |
| | 26.2.1.2 SECONDARY MEANS OF ESCAPE. IN ADDITION TO THE |
| | PRIMARY |
| | ROUTE, EACH SLEEPING ROOM AND LIVING AREA SHALL HAVE A |
| | SECOND |
| | MEANS OF ESCAPE IN ACCORDANCE WITH 24.2.2, UNLESS THE |
| | SLEEPING |
| | ROOM OR LIVING AREA HAS A DOOR LEADING DIRECTLY OUTSIDE |
| | THE |
| | BUILDING WITH ACCESS TO THE FINISHED GROUND LEVEL OR TO |
| | A STAIRWAY |
| | THAT MEETS THE REQUIREMENTS FOR EXTERIOR STAIRS IN |
| | 26.2.1.1.2. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS IN COMPLIANCE WITH THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) THE STAIRWAY FROM THE 2ND FLOOR APPEARS TO BE |
| | UNINCLOSED. |
| | |
| | PER NFPA 101, CH 26 |
| | |
| | 26.2.2 STAIRWAYS. |
| | 26.2.2.1 INTERIOR STAIRWAYS, OTHER THAN THOSE IN |
| | ACCORDANCE WITH |
| | 26.2.2.2 OR 26.2.2.3, SHALL COMPLY WITH 7.2.2.5.3 AND |
| | SHALL BE |
| | ENCLOSED BY FIRE BARRIERS HAVING A MINIMUM ?-HOUR FIRE |
| | RESISTANCE |
| | RATING, WITH ALL OPENINGS PROTECTED WITH SMOKE-ACTUATED |
| | AUTOMATIC-CLOSING OR SELF-CLOSING DOORS HAVING A FIRE |
| | RESISTANCE |
| | COMPARABLE TO THAT REQUIRED FOR THE ENCLOSURE. |
| | 26.2.2.2 WHERE AN INTERIOR STAIR CONNECTS THE STREET |
| | FLOOR WITH THE |
| | STORY NEXT ABOVE OR BELOW ONLY, BUT NOT WITH BOTH, THE |
| | INTERIOR |
| | STAIR SHALL BE REQUIRED TO BE ENCLOSED ONLY ON THE |
| | STREET FLOOR. |
| | 26.2.2.3 STAIRWAYS SHALL BE PERMITTED TO BE UNENCLOSED |
| | IN |
| | ACCORDANCE WITH 26.3.1.1.2 AND 26.3.1.1.3. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS IN COMPLIANCE WITH THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |