| Date |
Text |
| 2019-04-29 17:14:42 | PLUMBING 3RD REVIEW**DENIED**FL ST 553.80 (B)2B WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1) THE SHOWER DOES NOT COMPLY AS A STANDARD ROLL IN AS |
| | CALLED OUT ON SHEET P-1 AS THE SEAT/ CONTROLS IS NOT |
| | PERMITTED TO BE ADJACENT TO THE SINK. FBC-ACC 608.2.1. |
| | SHT DET-1 SHOWS HOW IT SHOULD BE IF THE SINK WAS ON THE |
| | OPPOSITE WALL.SEE FBC-ACC 608.2.2.1 EXCEPTION. |
| | |
| | 2) PROVIDE CLEAR FLOOR SPACE FOR THE SHOWER. I WAS NOT |
| | ABLE TO LOCATE IT ON ANY SHEETS. FBC 107.3.5 |
| | |
| | 3) SHT. P-2 DETAIL #1 SHOWER PAN DETAIL IS SHOWING A |
| | CURB 2"-9". CURB'S/ THRESHOLDS OVER 1/2" ARE NOT |
| | PERMITTED (ROLL IN). FBC-ACC 608.7 |
| | |
| | 4) DRINKING FOUNTAIN SHALL BE A HIGH/ LOW DRINKING |
| | FOUNTAIN. FBC-PLUMBING 410.3 |
| | |
| | 5) SHT DET-1 SHOWS THE WASHING MACHINES AND DRYERS AS |
| | HAVING A FORWARD APPROACH. PER FBC-ACC 611.2 ONLY A |
| | PARALLEL APPROACH IS PERMITTED. |
| | |
| | 6) SHOW ALL CLEAR FLOOR SPACE ON SHT.A-1. YOU ARE |
| | MISSING THE WASHING MACHINES, DRYERS, KITCHEN SINK, AND |
| | SHOWER. NOTE WASHING MACHINES AND DRYERS MUST BE |
| | PARALLEL. FBC 107.3.5 |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |
| | |