| Plan Review Notes For Permit 18110241 |
| Permit Number |
18110241 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-05-16 07:49:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PLEASE REFER TO EMAIL SENT 4/17/19 TO PAM EGAN, CC'D | | | ROBERT BROWN, STEVE KENNEDY, PATRICK O'CONNELL RA, | | | CAMILLE DAWSON, ROCK DESJARDINS, DANIEL USHER, DENIS | | | HOLMES, REBECCA MILLER WHERE YOU WERE INFORMED THAT | | | THIS IS NOT R4, SHOULD BE I-1, AND IS SUBJECT TO | | | ACCESSIBILITY. SEE SP1, OCCUPANCY CLASSIFICATION IS | | | STILL R4 ON THE PLAN. NOTE THAT R3/R4 IS FOR RESIDENTS | | | PERMANENT IN NATURE; UNDER 30 DAYS IS NOT CONSIDERED | | | PERMANENT. | | | | | | SEE ALSO PLUMBING COMMENTS REGARDING ACCESSIBILITY | | | REQUIREMENTS. | | | | | | 2. BASED ON DESCRIPTION OF SERVICES, IT APPEARS THAT | | | THIS RENOVATION IS TO COMPLY WITH THE REQUIREMENTS OF | | | FBC A 224, TRANSIENT LODGING ROOMS. FLORIDA SPECIAL | | | ROOM COMPLIANCE NOT CLEAR, UNABLE TO LOCATE | | | COMMUNICATION FEATURES TABLE 224.4, ALSO SEE 224.5 | | | DISPERSION. ONE ROOM WITH A SINGLE TWIN BED IS SHOWN AS | | | THE ACCESSIBLE ROOM; OTHER ROOMS ARE SHOWN WITH A FULL | | | BED. COMPLIANCE NOT CLEAR. | | | | | | | | | | | | |
|