| 2018-12-11 10:32:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: DENIED |
| | 1. PLUMBING PLANS SHALL BE STAMPED/SEALED AND SIGNED BY |
| | DESIGNER OF RECORD AS DESCRIBED BY WPB FBC 107.1 AND IN |
| | ACCORDANCE WITH FS 471 AND FAC 61G15. |
| | 2. PROVIDE A DETAILED SCOPE OF WORK IN ACCORDANCE WITH |
| | WPB FPC 107.2.1 WHICH ADDRESSING THE FOLLOWING |
| | COMMENTS. |
| | A) THE SANITARY BUILDING DRAIN BRANCH SERVICING THE |
| | KITCHEN AND LAUNDRY FACILITIES AND THE P-2 FIXTURE |
| | APPEAR NOT TO BE EXISTING, BUT RATHER, ADDED. PLEASE |
| | CLARIFY. |
| | B) PROVIDE SANITARY PLUMBING RISER DIAGRAM FOR NEW |
| | SANITARY BUILDING DRAIN BRANCH, P-2 FIXTURE AND POINTS |
| | OF CONNECTION. PROVIDE SIZING AND FIXTURE UNIT LOAD FOR |
| | EXISTING PIPING AND NEW FIXTURE UNIT LOAD (SEE FBC PL |
| | 709) BEING ADDED SHOWING COMPLIANCE WITH FBC PL 710. |
| | SHOW ALL FIXTURE DRAINS, BRANCHES, TRAPS AND VENTS. |
| | C) PROVIDE FLOOR PLAN AND RISER DIAGRAM OF NEW POTABLE |
| | WATER DISTRIBUTION AND POINT(S) OF CONNECTION. PROVIDE |
| | SIZING AND LOAD/DEMAND FOR NEW AND EXISTING PIPING |
| | SHOWING COMPLIANCE WITH FBC PL 604. |
| | D) PROVIDE LOCATION OF EXISTING BACKFLOW PREVENTER FOR |
| | THE WATER SUPPLY. PROVIDE DOCUMENTATION OF CURRENT |
| | CERTIFICATION FOR THE SAME. |
| | E) PROVIDE A FIXTURE SCHEDULE OF ALL AFFECTED FIXTURES |
| | REPLACED OR ADDED. SPECIFY SHOWER CONTROL VALVES AND |
| | VACUUM BREAKERS FOR HAND HELD SHOWERS. INDICATE ON THE |
| | PLAN WHICH FIXTURES ARE ADDED AND WHICH ARE BEING |
| | REPLACED. |
| | F) PROVIDE WATER HEATER SCHEDULE NOTING STORAGE |
| | CAPACITY AND ELECTRICAL CHARACTERISTICS. COORDINATE |
| | WITH ELECTRICAL DESIGN. PROVIDE WATER HEATER DETAIL, |
| | SHOWING COMPLIANCE WITH THE REQUIREMENTS OF FBC PL 504 |
| | AND 607.3. |
| | G) PROVIDE SHOWER PAN DETAIL, SHOWING COMPLIANCE WITH |
| | THE REQUIREMENTS OF FBC PL 417. |
| | H) PROVIDE DETAIL FOR WASHER BOX WITH FIXTURE DRAIN, |
| | TRAP AND WATER OUTLETS. SHOW COMPLIANCE WITH FBC 604.9. |
| | I) PROVIDE DETAIL FOR KITCHEN CABINET AND SINK SHOWING |
| | COMPLIANCE WITH FBC ACC 233, 809, 804 AND 606. |
| | J) PROVIDE DETAIL ON ICE LINE IF APPLICABLE. SHOW |
| | COMPLIANCE WITH FBC 604.9. |
| | K) SHOW DISHWASHER COMPLIANCE WITH FBC 604.9. |
| | 3. PROVIDE A SERVICE SINK IN ACCORDANCE WITH FBC PL |
| | TABLE 403.1 |
| | 4. PROVIDE A DRINKING FOUNTAIN IN ACCORDANCE WITH FBC |
| | PL TABLE 403.1. DRINKING FOUNTAIN SHALL BE BARRIER FREE |
| | IN ACCORDANCE WITH FBC ACC 211 AND 602. |
| | |
| | END OF COMMENTS |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| | ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | |