Plan Review Notes
Plan Review Notes For Permit 18110241
Permit Number 18110241
Review Stop P
Sequence Number 1
Notes
Date Text
2018-12-11 10:32:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 1. PLUMBING PLANS SHALL BE STAMPED/SEALED AND SIGNED BY
 DESIGNER OF RECORD AS DESCRIBED BY WPB FBC 107.1 AND IN
 ACCORDANCE WITH FS 471 AND FAC 61G15.
 2. PROVIDE A DETAILED SCOPE OF WORK IN ACCORDANCE WITH
 WPB FPC 107.2.1 WHICH ADDRESSING THE FOLLOWING
 COMMENTS.
 A) THE SANITARY BUILDING DRAIN BRANCH SERVICING THE
 KITCHEN AND LAUNDRY FACILITIES AND THE P-2 FIXTURE
 APPEAR NOT TO BE EXISTING, BUT RATHER, ADDED. PLEASE
 CLARIFY.
 B) PROVIDE SANITARY PLUMBING RISER DIAGRAM FOR NEW
 SANITARY BUILDING DRAIN BRANCH, P-2 FIXTURE AND POINTS
 OF CONNECTION. PROVIDE SIZING AND FIXTURE UNIT LOAD FOR
 EXISTING PIPING AND NEW FIXTURE UNIT LOAD (SEE FBC PL
 709) BEING ADDED SHOWING COMPLIANCE WITH FBC PL 710.
 SHOW ALL FIXTURE DRAINS, BRANCHES, TRAPS AND VENTS.
 C) PROVIDE FLOOR PLAN AND RISER DIAGRAM OF NEW POTABLE
 WATER DISTRIBUTION AND POINT(S) OF CONNECTION. PROVIDE
 SIZING AND LOAD/DEMAND FOR NEW AND EXISTING PIPING
 SHOWING COMPLIANCE WITH FBC PL 604.
 D) PROVIDE LOCATION OF EXISTING BACKFLOW PREVENTER FOR
 THE WATER SUPPLY. PROVIDE DOCUMENTATION OF CURRENT
 CERTIFICATION FOR THE SAME.
 E) PROVIDE A FIXTURE SCHEDULE OF ALL AFFECTED FIXTURES
 REPLACED OR ADDED. SPECIFY SHOWER CONTROL VALVES AND
 VACUUM BREAKERS FOR HAND HELD SHOWERS. INDICATE ON THE
 PLAN WHICH FIXTURES ARE ADDED AND WHICH ARE BEING
 REPLACED.
 F) PROVIDE WATER HEATER SCHEDULE NOTING STORAGE
 CAPACITY AND ELECTRICAL CHARACTERISTICS. COORDINATE
 WITH ELECTRICAL DESIGN. PROVIDE WATER HEATER DETAIL,
 SHOWING COMPLIANCE WITH THE REQUIREMENTS OF FBC PL 504
 AND 607.3.
 G) PROVIDE SHOWER PAN DETAIL, SHOWING COMPLIANCE WITH
 THE REQUIREMENTS OF FBC PL 417.
 H) PROVIDE DETAIL FOR WASHER BOX WITH FIXTURE DRAIN,
 TRAP AND WATER OUTLETS. SHOW COMPLIANCE WITH FBC 604.9.
 I) PROVIDE DETAIL FOR KITCHEN CABINET AND SINK SHOWING
 COMPLIANCE WITH FBC ACC 233, 809, 804 AND 606.
 J) PROVIDE DETAIL ON ICE LINE IF APPLICABLE. SHOW
 COMPLIANCE WITH FBC 604.9.
 K) SHOW DISHWASHER COMPLIANCE WITH FBC 604.9.
 3. PROVIDE A SERVICE SINK IN ACCORDANCE WITH FBC PL
 TABLE 403.1
 4. PROVIDE A DRINKING FOUNTAIN IN ACCORDANCE WITH FBC
 PL TABLE 403.1. DRINKING FOUNTAIN SHALL BE BARRIER FREE
 IN ACCORDANCE WITH FBC ACC 211 AND 602.
  
 END OF COMMENTS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  