| 2018-12-11 10:42:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | IT APPEARS THAT THE DRYERS WILL BE GAS OPERATED; A GAS |
| | PERMIT IS REQUIRED |
| | GAS COMMENTS FOR YOUR USE |
| | SUBMIT THE FOLLOWING PER WPB FBC 107.2.1 |
| | 1. SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES, |
| | TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS |
| | OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE |
| | SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE |
| | SYSTEM. FBC FG 402.4.1, 402.4.2 |
| | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | 3. TYPE OF GAS (LP OR NATURAL). |
| | 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE FBC FG SECS.401.8, |
| | 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE FBC FG |
| | 402.4.1, 402.4.2 |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER FBC FG |
| | 304.1 |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER FBC FG 402.1, 402.4.3 THRU 402. |
| | 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG |
| | 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FBC FG305.1. |
| | 9. SUBMIT APPLICABLE SIZING TABLES USED TO SIZE THE GAS |
| | SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING |
| | WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER |
| | STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| | SYSTEM. REFER TO THE FBC FG 401.4, 401.8, 402.3, AND |
| | TABLES 402.4 (1) THRU 402.4 (37) |
| | 11. SHOW THE LOCATION OF ANY AND ALL MP (STEP-DOWN) |
| | REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. FBC FG 409.4, |
| | |
| | JERALD SMITH |