Plan Review Notes
Plan Review Notes For Permit 18110241
Permit Number 18110241
Review Stop G
Sequence Number 1
Notes
Date Text
2018-12-11 10:42:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 IT APPEARS THAT THE DRYERS WILL BE GAS OPERATED; A GAS
 PERMIT IS REQUIRED
 GAS COMMENTS FOR YOUR USE
 SUBMIT THE FOLLOWING PER WPB FBC 107.2.1
 1. SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES,
 TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS
 OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE
 SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE
 SYSTEM. FBC FG 402.4.1, 402.4.2
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 3. TYPE OF GAS (LP OR NATURAL).
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC FG SECS.401.8,
 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE FBC FG
 402.4.1, 402.4.2
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER FBC FG
 304.1
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER FBC FG 402.1, 402.4.3 THRU 402.
 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FBC FG305.1.
 9. SUBMIT APPLICABLE SIZING TABLES USED TO SIZE THE GAS
 SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING
 WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER
 STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE FBC FG 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37)
 11. SHOW THE LOCATION OF ANY AND ALL MP (STEP-DOWN)
 REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. FBC FG 409.4,
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  