| Plan Review Notes For Permit 18110204 |
| Permit Number |
18110204 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-11-13 11:07:31 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 1811 | | | REVIEWED: NOVEMBER 13, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | | | | 1. NOA 12-1204.03 ID EXPIRED. | | | PLEASE PROVIDE CURRENT PRODUCT APPROVAL FOR SHINGLE TO | | | BE INSTALLED. | | | ALSO, WHAT IS ROOF PITCH MINIMUM FOR THIS SLOPING | | | SHINGLE ROOF? | | | | | | 2. [FBC R905.2.2] [FBC R905.1.1]FOR ROOF SLOPES FROM | | | TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND | | | LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL | | | (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED. | | | PLEASE VERIFY WITH EXISTING ROOF SLOPE IF THIS CODE | | | APPLIES TO ANY AREA OF EXISTING ROOF. | | | | | | |
|