| Plan Review Notes For Permit 18110199 |
| Permit Number |
18110199 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-02-07 15:16:09 | APPROVED | | | PROVISO | | | 1. THE CIRCUIT VENTED BRANCH FOR THE 5 PEDICURE SPA | | | CHAIRS REQUIRES THE VENT CONNECTION BETWEEN THE TWO | | | MOST UPSTREAM FIXTURE DRAIN AND A RELIEF VENT | | | DOWNSTREAM OF THE FIXTURES PER FBC PL 914.2 & 914.4 | | | 2. PROVIDE ACCESS TO THE INTERCEPTOR FOR THE WASHER | | | THROUGH THE BACKSIDE OF THE WALL PER FBC PL 1003.10 | | | |
|