| 2018-12-27 12:44:31 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE DETAIL FOR THE WATER FOUNTAIN WITH |
| | DIMENSIONS COMPILING WITH BC ACC 602.2, 602.4, 602.7 |
| | |
| | 2. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM |
| | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. PER FBC |
| | ACC 604.7 |
| | |
| | 3. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE. PER FBC ACC 609.4 |
| | |
| | 4. A SERVICE SINK IS REQUIRED INDICATE ON THE PLAN |
| | LOCATION. PER FBC PL TABLE 403.1 |
| | |
| | 5. TWO ACCESSIBLE BATHROOMS ARE REQUIRED THEY SHALL BE |
| | SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX. PER |
| | FBC PL TABLE 403.1 AND 403.2 FBC ACC 213 |
| | |
| | 6. THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN |
| | THE TWO MOST UPSTREAM FIXTURE DRAINS. FOR THE 5 |
| | PEDICURE SPA CHARS. PER FBC 914.2 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |