2018-11-29 17:20:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110199
 11/29/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PROVIDE THE SEQUENCE OF OPERATION FOR THE
 SALON EXHAUST SYSTEM- TABLE 403.3.1.1 FOOTNOTE H, AND
 SECTION 501.3.2 FBC M.
  
 2) M-1 & M-2: PROVIDE A DETAIL SHOWING HOW THE MANICURE
 EXHAUST INLETS WILL BE ATTACHED TO THE TABLES- SECTION
 502.20 FBC M.
  
 3) M-1 & M-2:SHOW THE DIMENSIONS OF THE ACCESS PANELS
 AND VERIFY THEY ARE LARGE ENOUGH TO REMOVE AND REPLACE
 THE AIR HANDLERS ABOVE THE CEILINGS- SECTION 306.1 FBC
 M.
  
 4) M-1: RECIRCULATION OF AIR FROM THE SALON TO THE
 BREAKROOM AND RESTOOM IS PROHIBITED PER TABLE 403.3.1.1
 FOOTNOTE B.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE GULFSTREAM AIR VENT
 SYSTEM- SECTION 304.1 FBC M.
  
 6) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE WALL BRACKET AND CONDENSER
 INSTALLATION- SECTION 301.15 FBC M & SECTION 1609 FBC
 B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  