Plan Review Notes
Plan Review Notes For Permit 18110176
Permit Number 18110176
Review Stop P
Sequence Number 2
Notes
Date Text
2019-01-22 08:04:00RE: GREASE INTERCEPTOR CALCULATIONS; PER WPB FBC
 107.3.4.1 MAY BE PROVIDED AS DEFERRED SUBMITTALS PRIOR
 TO ISSUE OF GREASE INTERCEPTOR PERMIT. RECEIVED AND
 APPROVED 1/22/2019
2019-01-17 15:40:15APPROVED
 PROVISO
 1. RE: MEN'S TOILET ROOM; URINAL SHALL NOT DISCHARGE
 INTO THE WET VENT FOR THE WATER CLOSET PER FBC PL
 912.1. SEE REDLINED DRAWINGS 3.0P AND 3.1P FOR
 CORRECTION.
 2. RE: GREASE INTERCEPTOR CALCULATIONS; PER WPB FBC
 107.3.4.1 MAY BE PROVIDED AS DEFERRED SUBMITTALS PRIOR
 TO ISSUE OF GREASE INTERCEPTOR PERMIT.
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3 PERFBC 416.5.
 4. BACKFLOW PREVENTION ISREQUIRED FOR COFFEEMAKERS, ICE
 MAKERS AND FILTERS PER FBC 608.2.