| Plan Review Notes For Permit 18110176 |
| Permit Number |
18110176 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-01-22 08:04:00 | RE: GREASE INTERCEPTOR CALCULATIONS; PER WPB FBC | | | 107.3.4.1 MAY BE PROVIDED AS DEFERRED SUBMITTALS PRIOR | | | TO ISSUE OF GREASE INTERCEPTOR PERMIT. RECEIVED AND | | | APPROVED 1/22/2019 | | 2019-01-17 15:40:15 | APPROVED | | | PROVISO | | | 1. RE: MEN'S TOILET ROOM; URINAL SHALL NOT DISCHARGE | | | INTO THE WET VENT FOR THE WATER CLOSET PER FBC PL | | | 912.1. SEE REDLINED DRAWINGS 3.0P AND 3.1P FOR | | | CORRECTION. | | | 2. RE: GREASE INTERCEPTOR CALCULATIONS; PER WPB FBC | | | 107.3.4.1 MAY BE PROVIDED AS DEFERRED SUBMITTALS PRIOR | | | TO ISSUE OF GREASE INTERCEPTOR PERMIT. | | | 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE | | | THAT CONFORMS TO ASSE 1070 OR CSA B125.3 PERFBC 416.5. | | | 4. BACKFLOW PREVENTION ISREQUIRED FOR COFFEEMAKERS, ICE | | | MAKERS AND FILTERS PER FBC 608.2. |
|