2018-11-27 16:39:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110176
 11/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.0M: PLEASE LABEL THE RTU'S ON THE PLAN AS
 EITHER NEW OR EXISTING. IT APPEARS BY THE SCHEDULE THAT
 ONLY RTU-1 IS BEING REPLACED. IS THAT CORRECT, OR ARE
 ALL THE RTU'S BEING REPLACED?
  
 2) 4.0M: PLEASE INCLUDE EF-3 IN THE AIR BALANCE
 CALCULATION.
  
 3) 4.0M: PLEASE INCLUDE THE PIZZA OVEN AND EXHAUST
 SYSTEM IN THE SEPARATE PERMIT LIST.
  
 4) 4.0M: ALTHOUGH SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOOD, PIZZA OVEN AND FIRE SUPPRESSION
 SYSTEM, PLEASE BE ADVISED THAT SECTION 508.1.1 FBC M IS
 APPLICABLE TO THIS PROJECT.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 6) 4.0M: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 7) 4.0M: CLARIFY IF THE BTUH LOAD OF THE PIZZA OVEN IS
 INCLUDED IN THE TOTAL BTUH LOAD SHOWN IN THE COMBUSTION
 AIR CALCULATION- SECTION 304.9 FBC FG.
  
 8) SHEETS 1.2A & M4.0M: ALTHOUGH UNDER SEPARATE PERMIT,
 THE WOOD-FIRED PIZZA OVEN SHALL BE UL 2162 LISTED AND
 LABELED PER SECTION 917.1 FBC M. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS OR A UL CERTIFICATE TO
 VERIFY COMPLIANCE.
  
 9) M4.0M: THE PLAN INDICATES A B-VENT WILL BE USED AS
 AN EXHAUST FLUE FOR THE OVEN. THIS TYPE OF VENT IS
 TYPICALLY NOT PERMITTED FOR HIGH HEAT COOKING
 APPLIANCES. PLEASE INDICATE THE CORRECT FLUE VENT PER
 THE MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE OVEN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER