| 2018-11-07 15:26:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET C 1 - THERE IA AN INDICATION THAT THIS IS A |
| | MERCANTILE OCCUPANCY. |
| | |
| | PER THE FLORIDA FIRE PREVENTION CODE, 6TH ED THIS IS AN |
| | ASSEMBLY OCCUPANCY. |
| | |
| | NFPA 101, CHAPTER 6, OCCUPANCY CLSSIFICATION |
| | |
| | 6.1.2.1* DEFINITION ? ASSEMBLY OCCUPANCY. AN OCCUPANCY |
| | (1) USED |
| | FOR A GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION, |
| | WORSHIP, |
| | ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING |
| | TRANSPORTATION, OR |
| | SIMILAR USES; OR (2) USED AS A SPECIAL AMUSEMENT |
| | BUILDING, REGARDLESS OF |
| | OCCUPANT LOAD. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 2) SHEET C 1 - THERE ARE INDICATION OF INCORRECT |
| | REFERNCES TO THE FLORIDA FIRE PREVEENTION CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2013 EDITION. |
| | |
| | PLEASE REIVEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 3) SHEET 1.1A - THERE IS A PIZZA OVEN INDICATED. THERE |
| | ARE NO MANUFACTURES SPECIFICATION AND REQUIREMENT |
| | SHEETS PROVIDED. |
| | |
| | PLEASE PROVIDE THE PROPOSED PIZZA OVEN SPEC SHEETS. |
| | |
| | |
| | |
| | 4) SHEET 1.1A - THERE IS HOOD AND SUPPRESSION SYSTEM |
| | INDICATED. THESE SYSTEMS SHALL BE PROVIDED AND |
| | INSTALLED PER NFPA 96, 2014 ED., UNDER SEPARATE SHOP |
| | DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDEGMENT AND COMPLIANCE. |
| | |
| | |
| | |
| | 5) SHEET 1.2A - THERE IS AN INDICATION OF A WOOD |
| | BURNING PIZZA OVEN, PLEASE PROVIDE FOR # 3 ABOVE AS |
| | WELL AS WHERE AND HOW MUCH WOOD WILL BE STORED ON SITE. |
| | |
| | PLEASE REVIEW NFPA 211, STANDARD FOR CHIMNEYS, |
| | FIREPLACES, VENTS, AND SOLID FUEL?, BURNING APPLIANCES, |
| | 2013 EDITION. |
| | |
| | PLEASE REVIEW AND PROVIDE FOR THE REQUIREMENTS BASED ON |
| | YOUR NEEDS AND PROVIDE APPLICABLE SPECIFIC SITE DETAILS |
| | AND NARRATIVE NOTES. |
| | |
| | |
| | |
| | 6) SHEET 1.3A - THERE IS A NOTE, # 6, INDICATING DUCT |
| | SMOKE DETECTORS WITH AN INCORRECT EDITION. |
| | |
| | AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B, |
| | 2015 EDITION. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 7) SHEET 1.3A - THERE IS A NOTE, # 11 INDICATING A |
| | OCCUPANCY LOAD SIGN OF 88. THERE IS A CONFLICT WITH THE |
| | OCCUPANCY LOAD CALCULATION TABLE OF 109 + 21 BAR = 130 |
| | |
| | PLEAE REVIEW AND EXPLAIN AND CORRECT. |
| | |
| | |
| | |
| | 8) SHEET 1.3A - SHEET C 1 & 1.3A - SHEET C 1 INDICATES |
| | 150 SEATS. SHEETS 1.3A INDICATES 134 ACTUAL SEATA AND |
| | 15 BAR STOOLS FOR A TOTAL OF 149. |
| | |
| | THE OCCUPANCY LOAD CALCULATIONS INDICATED 109 TOTAL |
| | PEOPLE FOR THE PROPOSEDSQ FT. WHICH INCLUDES THE BAR. |
| | |
| | THERE ARE MULTIPLE CONFLICTS WITH THE OCCUPANCY LOAD |
| | CALCULATIONS AND INFO ON MULTIPLE SHEETS. |
| | |
| | PLEASE REVIEW AND CORRECT AND JUSTIFY WITH SPECIFIC |
| | CODE REFERENCES. |
| | |
| | |
| | |
| | 9) SHEET 1.3A - THERE ARE NO DIMENSIONS OS AISLES AND |
| | BETWEEN SEATS AND TABLES THAT MEET THE REQUIRMENTS OF |
| | THE CODE. |
| | |
| | PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES. |
| | |
| | 12.2.5.8.2* THE WIDTH OF AISLES SERVING SEATING AT |
| | TABLES SHALL BE |
| | NOT LESS THAN 44 IN. (1120 MM) WHERE SERVING AN |
| | OCCUPANT LOAD |
| | EXCEEDING 50, AND 36 IN. (915 MM) WHERE SERVING AN |
| | OCCUPANT |
| | LOAD OF 50 OR FEWER. |
| | 12.2.5.8.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A |
| | TABLE AND |
| | AN AISLE, THE MEASUREMENT OF REQUIRED CLEAR WIDTH OF |
| | THE AISLE SHALL |
| | BE MADE TO A LINE 19 IN. (485 MM), MEASURED |
| | PERPENDICULARLY TO |
| | THE EDGE OF THE TABLE, AWAY FROM THE EDGE OF SAID |
| | TABLE. |
| | 12.2.5.9 APPROVAL OF LAYOUTS. |
| | 12.2.5.9.1 WHERE REQUIRED BY THE AUTHORITY HAVING |
| | JURISDICTION, |
| | PLANS DRAWN TO SCALE SHOWING THE ARRANGEMENT OF |
| | FURNISHINGS OR |
| | EQUIPMENT SHALL BE SUBMITTED TO THE AUTHORITY BY THE |
| | BUILDING |
| | OWNER, MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE |
| | CONFORMANCE |
| | WITH THE PROVISIONS OF 12.2.5. |
| | |
| | PLEASE REVIEW AND PROVIDE THE REQUIRED DIMENSIONS |
| | |
| | |
| | 10) SHEET 1.3A - THERE ARE 14 STOOLS INDICATED AT THE |
| | BAR. THE OCCUPANCY LOEAD INDICATES 21. WHICH IS |
| | CORRECT? |
| | |
| | PLEASE PROVIDE FOR THE ACCURATE ACCOUNTING OF BAR |
| | STOOLS PER THE CALULATION AND # 8 ABOVE. |
| | |
| | |
| | |
| | 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |