| Plan Review Notes For Permit 18110176 |
| Permit Number |
18110176 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-11-19 16:59:34 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | PAGE 1.5A | | | | | | NO TYPE "H" FIXTURE | | | TYPE "B" SHOWS NO WATTAGE | | | | | | PAGE 2.0E | | | | | | NEED AIC CALCULATION FOR NEW K7 AND PANELS | | | CIRCUIT B-1 SHOW AUDIO VISUAL, NEXT PAGE SHOWS ALL THE | | | LIGHTING ON THIS CORCUIT. | | | CIRCUIT B-SHOWS AS A SPARE | | | | | | PAGE 2.1E | | | | | | B-3 IS LIGHTING CIRCUIT | | | B-15 IS TRACK CIRCUIT | | | | | | PAGE 2.2E | | | | | | ALL RTUS HAVE SAME CIRCUIT DESIGNATION | | | WINEN ACC NO CKT DESIGNATION | | | SUPPLY FAN AND EXHAUST FAN SHOW SAME CIRCUIT | | | DESIGNATION | | | | | | | | | | | | |
|