Plan Review Notes
Plan Review Notes For Permit 18110176
Permit Number 18110176
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-07 10:50:44****CORRECTIONS****
 W.P.B. PERMIT: 18110176
 REVIEWED: DECEMBER 7, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1. [FBC ENERGY C401.2]APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 A. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 B. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 C. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 2. [FBC EXISTING 501]STATE CLASSIFICATION FOR WORK
 BEING PERFORMED.
 STATE THE EXISTING OCCUPANCY OF THE BUILDING.
 THE CLASSIFICATION SHOULD BE CHANGE OF OCCUPANCY OR
 LEVEL OF ALTERATION.
  
 3. [FBC 303.3]ASSEMBLY GROUP A-2
 SHOW OCCUPANCY AS A-2 FOR THE 1634 SQ. FT.
 THE AMOUNT OF OCCUPANT LOAD IN THE COMMERCIAL KITCHEN
 SHOULD BE DETERMINED IN TABLE 1004.1.2. COMMERCIAL
 KITCHENS USE 200 SQ. FT. GROSS.
 A) PLEASE UPDATE SHEET 1.3A TO SHOW OCCUPANCY TYPES AND
 OCCUPANT LOADS.
 B) ADJUST NOTE #11 TO MATCH OCCUPANT LOAD.
  
 4. [FBC 107.3.5.3]SHEET C-1
 A) UPDATE CODE VERSIONS IN GENERAL NOTES TO USE THE
 FLORIDA BUILDING CODE, 6TH EDITION (2017)
 B) UNDER OCCUPANCY TYPE CHANGE TO A-2.
 C) CHANGE NUMBER OF SEATS TO MATCH 1.3A
 D) ADD SHEETS 1.5A AND 4.1M TO INDEX
  
  
 5. [FBC P403.2]SEPARATE FACILITIES. WHERE PLUMBING
 FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
 LABEL MENS AND WOMENS RESTROOMS.
  
 6. [FBC 456.3.2.2]PUBLIC BATHROOMS SHALL BE COMPLETELY
 ENCLOSED AND SHALL HAVE TIGHT-FITTING, SELF-CLOSING
 DOORS.
 UPDATE DOOR SCHEDULE AS APPLICABLE.
  
 7. [FBC 1210.2.2]WALLS AND PARTITIONS. WALLS AND
 PARTITIONS
 WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND
 WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO
 A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE
 FLOOR,
 AND EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED
 IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED
 BY MOISTURE.
  
 8. [FBC TABLE 2902.1]WHERE IS SERVICE SINK LOCATED?
  
 9. [FBC A206.1]GENERAL.
 ACCESSIBLE ROUTES SHALL BE PROVIDED IN ACCORDANCE WITH
 206 AND SHALL COMPLY WITH CHAPTER 4.
 A) PROVIDE SITE PLAN WITH PARKING LAYOUT.
 B) SHOW ACCESSIBLE PATH FROM PARKING TO ACCESSIBLE
 ENTRY.
  
 10. [FBC A226.1]THE ACCESSIBILITY CODE REQUIRES 0.05 %
 OF ALL SEATING TO BE ACCESSIBLE.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
 SHOW 5% OF SEATING TO COMPLY WITH 226.1 AND 902.
  
 11. [FBC A(FIGURE 404.2.4.1)]SHOW DOOR CLEARANCE IN
 RESTROOMS FOR APPLICABLE APPROACH WITH CLOSER AND
 LATCH.
  
 12. [FBC 107.3.5]SECTION 2-1.2A DOESN?T MATCH FLOOR
 PLAN 1.0A WHERE IT IS CALLED OUT.
 HOW DOES WOOD BURNING PIZZA OVEN WORK IN PLAN VIEW?
  
 13. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVAL FOR
 OPENING #6, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
  
 14. [FBC 107.5.1]EXPIRED PERMITS NEED TO BE ADDRESSED.
 SEE THE EXPIRED PERMITS LISTED BELOW.
 17080987, 15070429, 14030723, 11100171, 10090416 AND
 09070635.
 ANY OF THESE THAT AFFECT THIS PROJECT SHOULD BE
 ADDRESSED PRIOR TO PERMIT ISSUANCE AND THE PERMITS FROM
 OTHER UNITS CAN BE A PROVISO OF PERMIT TO BE COMPLETED
 PRIOR TO CERTIFICATE OF OCCUPANCY.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  
2018-11-21 14:30:47BUILDING PLANS EXAMINER, PLEASE NOTE THERE ARE SEVERAL
 EXPIRED PERMITS ON RECORD FOR THIS SPACE. PLEASE
 COORDINATE WITH APPLICANT TO ADDRESS THE STATUS OF EACH
 AND EVALUATE RESOLUTION.