Plan Review Notes
Plan Review Notes For Permit 18110160
Permit Number 18110160
Review Stop E
Sequence Number 1
Notes
Date Text
2018-12-14 14:54:14FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO SMOKE ALARMS, NO CO ALARMS SHOWN FBC R314, FBC R315
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. FBC R314.3, 315.1; FBC 107.2.1
  
 OUTLET SPACING MISSING IN SEVERAL AREAS
  
 E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO
 THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR
 LINE OF ANY WALL SPACE IS MORE THAN 6 FEET (1829 MM),
 FROM A RECEPTACLE OUTLET. [210.52(A)(1)]
  
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING: [210.52(A)(2)]
 1. 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN
 WIDTH, INCLUDING SPACE MEASURED AROUND CORNERS, AND
 THAT IS UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND
 SIMILAR OPENINGS, FIREPLACES, AND FIXED CABINETS.
 2. 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS, EXCLUDING SLIDING PANELS.
 3. 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS
  
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH
 CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2,
 RE3902
  
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE
 PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)]
  
 E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR
 PERSONNEL. [210.8(A)(9)]
  
 E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT.
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE
 PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN
 DWELLING UNIT LOCATIONS. [210.8(D)]
  
 OUTLETS MISSING ON FRONT AND BACK OF BUILDING
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK
 OF EACH DWELLING UNIT HAVING DIRECT ACCESS TO GRADE
 LEVEL. BALCONIES, DECKS, AND PORCHES THAT ARE
 ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT SHALL HAVE
 AT LEAST ONE RECEPTACLE OUTLET INSTALLED WITHIN
 THE PERIMETER OF THE BALCONY, DECK, OR PORCH. THE
 RECEPTACLE SHALL BE LOCATED NOT MORE THAN 6 FEET, 6
 INCHES (1981 MM) ABOVE THE BALCONY, DECK, OR PORCH
 SURFACE. [210.52(E)]
  
 IS THERE AN AC SYSTEM?????