| 2018-12-14 14:54:14 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | NO SMOKE ALARMS, NO CO ALARMS SHOWN FBC R314, FBC R315 |
| | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| | CODE. FBC R314.3, 315.1; FBC 107.2.1 |
| | |
| | OUTLET SPACING MISSING IN SEVERAL AREAS |
| | |
| | E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO |
| | THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR |
| | LINE OF ANY WALL SPACE IS MORE THAN 6 FEET (1829 MM), |
| | FROM A RECEPTACLE OUTLET. [210.52(A)(1)] |
| | |
| | E3901.2.2 WALL SPACE. |
| | AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE |
| | FOLLOWING: [210.52(A)(2)] |
| | 1. 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN |
| | WIDTH, INCLUDING SPACE MEASURED AROUND CORNERS, AND |
| | THAT IS UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND |
| | SIMILAR OPENINGS, FIREPLACES, AND FIXED CABINETS. |
| | 2. 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR |
| | WALLS, EXCLUDING SLIDING PANELS. |
| | 3. 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS |
| | RAILINGS AND FREESTANDING BAR-TYPE COUNTERS |
| | |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH |
| | CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2, |
| | RE3902 |
| | |
| | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, |
| | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| | SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| | LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE |
| | PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] |
| | |
| | E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY AREAS SHALL |
| | HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR |
| | PERSONNEL. [210.8(A)(9)] |
| | |
| | E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT. |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE |
| | PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN |
| | DWELLING UNIT LOCATIONS. [210.8(D)] |
| | |
| | OUTLETS MISSING ON FRONT AND BACK OF BUILDING |
| | |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK |
| | OF EACH DWELLING UNIT HAVING DIRECT ACCESS TO GRADE |
| | LEVEL. BALCONIES, DECKS, AND PORCHES THAT ARE |
| | ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT SHALL HAVE |
| | AT LEAST ONE RECEPTACLE OUTLET INSTALLED WITHIN |
| | THE PERIMETER OF THE BALCONY, DECK, OR PORCH. THE |
| | RECEPTACLE SHALL BE LOCATED NOT MORE THAN 6 FEET, 6 |
| | INCHES (1981 MM) ABOVE THE BALCONY, DECK, OR PORCH |
| | SURFACE. [210.52(E)] |
| | |
| | IS THERE AN AC SYSTEM????? |