| Notes |
| Date |
Text |
| 2018-11-15 10:35:06 | PROVISO: | | | [FBC R905.2.2] [FBC R905.1.1]FOR ROOF SLOPES FROM TWO | | | UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND LESS | | | THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL (4:12), | | | DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED. | | | SLOPE IS INDICATED AS 3.5:12, THIS WOULD REQUIRE DOUBLE | | | LAYER OF UNDERLAYMENT. |
|