| 2018-12-04 15:29:55 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 107.2.1 PLANS ARE NOT OF SUFFICIENT CLARITY AND | | | PLEASE ADD A TITLE BLOCK WITH THE ENGINEER'S | | | INFORMATION IN ADDITION TO THE ENGINEER'S SIGNATURE AND | | | SEAL. | | | FBC 107.2.5 THE SITE PLAN DOES NOT SHOW FLOOD ZONE | | | INFORMATION. THIS AREA APPEARS TO BE WITHIN A FLOOD | | | ZONE (BELOW 14.2 ELEVATION). PLEASE SHOW PROPOSED | | | ELEVATIONS OF FOUNDATION. |
|