Plan Review Notes
Plan Review Notes For Permit 18110099
Permit Number 18110099
Review Stop M
Sequence Number 1
Notes
Date Text
2018-11-28 09:32:58MECHANICAL PLAN REVIEW FAIL
  
  
 1 - BEDROOMS NEED RETURN AIR. PER 2017 FLORIDA BUILDING
 CODE - RESIDENTIAL SEC. M1602.3 BALANCED RETURN AIR.
 2 - PLEASE PROVIDE MANUFACTURER SPECIFICATION FOR
 KITCHEN HOOD. PER 2017 FLORIDA BUILDING CODE -
 RESIDENTIAL SEC.M1503.4 MAKEUP AIR REQUIRED.
  